Plan Review Notes
Plan Review Notes For Permit 15080126
Permit Number 15080126
Review Stop M
Sequence Number 1
Notes
Date Text
2015-08-19 13:01:461ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080126
 8/19/15
  
 1) THE SUBMITTED PLANS DO NOT CONTAIN ANY DETAILS OR
 SPECIFICATIONS FOR THE REQUIRED NAIL SALON EXHAUST
 SYSTEMS. PLEASE REFER TO TABLE 403.3 FBC-14 MECHANICAL-
 AN EXHAUST RATE OF 0.6 IS REQUIRED FOR NAIL SALONS. SEE
 FOOTNOTES B AND H REPRINTED BELOW AS THEY APPLY TO NAIL
 SALONS.
 B. MECHANICAL EXHAUST REQUIRED AND THE RECIRCULATION OF
 AIR FROM SUCH SPACES IS PROHIBITED (SEE SECTION
 403.2.1, ITEM 3).
 H. FOR NAIL SALONS, EACH NAIL STATION SHALL BE PROVIDED
 WITH A SOURCE CAPTURE SYSTEM CAPABLE OF EXHAUSTING NOT
 LESS THAN 50 CFM PER STATION.
  
 SECTION 403.2.1 RECIRCULATION OF AIR.
 THE OUTDOOR AIR REQUIRED BY SECTION 403.3 SHALL NOT BE
 RECIRCULATED. AIR IN EXCESS OF THAT REQUIRED BY SECTION
 403.3 SHALL NOT BE PROHIBITED FROM BEING RECIRCULATED
 AS A COMPONENT OF SUPPLY AIR TO BUILDING SPACES, EXCEPT
 THAT:
 1. VENTILATION AIR SHALL NOT BE RECIRCULATED FROM ONE
 DWELLING TO ANOTHER OR TO DISSIMILAR OCCUPANCIES.
 2. SUPPLY AIR TO A SWIMMING POOL AND ASSOCIATED DECK
 AREAS SHALL NOT BE RECIRCULATED UNLESS SUCH AIR IS
 DEHUMIDIFIED TO MAINTAIN THE RELATIVE HUMIDITY OF THE
 AREA AT 60 PERCENT OR LESS. AIR FROM THIS AREA SHALL
 NOT BE RECIRCULATED TO OTHER SPACES WHERE MORE THAN 10
 PERCENT OF THE RESULTING SUPPLY AIRSTREAM CONSISTS OF
 AIR RECIRCULATED FROM THESE SPACES.
 3. WHERE MECHANICAL EXHAUST IS REQUIRED BY NOTE B IN
 TABLE 403.3, RECIRCULATION OF AIR FROM SUCH SPACES
 SHALL BE PROHIBITED. ALL AIR SUPPLIED TO SUCH SPACES
 SHALL BE EXHAUSTED, INCLUDING ANY AIR IN EXCESS OF THAT
 REQUIRED BY TABLE 403.3.
 4. WHERE MECHANICAL EXHAUST IS REQUIRED BY NOTE G IN
 TABLE 403.3, MECHANICAL EXHAUST IS REQUIRED AND
 RECIRCULATION IS PROHIBITED WHERE MORE THAN 10 PERCENT
 OF THE RESULTING SUPPLY AIRSTREAM CONSISTS OF AIR
 RECIRCULATED FROM THESE SPACE
  
 PLEASE NOTE THAT ITEM 3 PRINTED ABOVE IS APPLICABLE TO
 NAIL SALON SYSTEMS- PROVIDE AN EXHAUST SYSTEM THAT IS
 IN COMPLIANCE.
  
 2) PLEASE REVIEW SECTION C403.2.6 AND TABLE C403.2.6
 FBC-14 ENERGY CONSERVATION AND SHOW COMPLIANCE AS
 APPLICABLE TO THE REQUIRED MAKEUP AIR FOR THE EXHAUST
 SYSTEM(S).
 3) THE SUBMITTED ENERGY COMPLIANCE FORM 506-2010 IS
 OUTDATED FOR THE NEW 2014 FLORIDA BUILDING CODE CYCLE.
 PLEASE UPDATE THE SOFTWARE AND SUBMIT A VALID UP TO
 DATE PRINTOUT.
  
 AS THE SUBMITTED PLANS ARE INCOMPLETE, A THOROUGH
 REVIEW CANNOT BE ACCOMPLISHED AT THIS TIME.
 PLEASE NOTE THAT ADDITIONAL COMMENTS MAY FOLLOW AFTER
 THE REVISED PLANS HAVE BEEN SUBMITTED FOR REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  