| 2015-08-19 13:01:46 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15080126 |
| | 8/19/15 |
| | |
| | 1) THE SUBMITTED PLANS DO NOT CONTAIN ANY DETAILS OR |
| | SPECIFICATIONS FOR THE REQUIRED NAIL SALON EXHAUST |
| | SYSTEMS. PLEASE REFER TO TABLE 403.3 FBC-14 MECHANICAL- |
| | AN EXHAUST RATE OF 0.6 IS REQUIRED FOR NAIL SALONS. SEE |
| | FOOTNOTES B AND H REPRINTED BELOW AS THEY APPLY TO NAIL |
| | SALONS. |
| | B. MECHANICAL EXHAUST REQUIRED AND THE RECIRCULATION OF |
| | AIR FROM SUCH SPACES IS PROHIBITED (SEE SECTION |
| | 403.2.1, ITEM 3). |
| | H. FOR NAIL SALONS, EACH NAIL STATION SHALL BE PROVIDED |
| | WITH A SOURCE CAPTURE SYSTEM CAPABLE OF EXHAUSTING NOT |
| | LESS THAN 50 CFM PER STATION. |
| | |
| | SECTION 403.2.1 RECIRCULATION OF AIR. |
| | THE OUTDOOR AIR REQUIRED BY SECTION 403.3 SHALL NOT BE |
| | RECIRCULATED. AIR IN EXCESS OF THAT REQUIRED BY SECTION |
| | 403.3 SHALL NOT BE PROHIBITED FROM BEING RECIRCULATED |
| | AS A COMPONENT OF SUPPLY AIR TO BUILDING SPACES, EXCEPT |
| | THAT: |
| | 1. VENTILATION AIR SHALL NOT BE RECIRCULATED FROM ONE |
| | DWELLING TO ANOTHER OR TO DISSIMILAR OCCUPANCIES. |
| | 2. SUPPLY AIR TO A SWIMMING POOL AND ASSOCIATED DECK |
| | AREAS SHALL NOT BE RECIRCULATED UNLESS SUCH AIR IS |
| | DEHUMIDIFIED TO MAINTAIN THE RELATIVE HUMIDITY OF THE |
| | AREA AT 60 PERCENT OR LESS. AIR FROM THIS AREA SHALL |
| | NOT BE RECIRCULATED TO OTHER SPACES WHERE MORE THAN 10 |
| | PERCENT OF THE RESULTING SUPPLY AIRSTREAM CONSISTS OF |
| | AIR RECIRCULATED FROM THESE SPACES. |
| | 3. WHERE MECHANICAL EXHAUST IS REQUIRED BY NOTE B IN |
| | TABLE 403.3, RECIRCULATION OF AIR FROM SUCH SPACES |
| | SHALL BE PROHIBITED. ALL AIR SUPPLIED TO SUCH SPACES |
| | SHALL BE EXHAUSTED, INCLUDING ANY AIR IN EXCESS OF THAT |
| | REQUIRED BY TABLE 403.3. |
| | 4. WHERE MECHANICAL EXHAUST IS REQUIRED BY NOTE G IN |
| | TABLE 403.3, MECHANICAL EXHAUST IS REQUIRED AND |
| | RECIRCULATION IS PROHIBITED WHERE MORE THAN 10 PERCENT |
| | OF THE RESULTING SUPPLY AIRSTREAM CONSISTS OF AIR |
| | RECIRCULATED FROM THESE SPACE |
| | |
| | PLEASE NOTE THAT ITEM 3 PRINTED ABOVE IS APPLICABLE TO |
| | NAIL SALON SYSTEMS- PROVIDE AN EXHAUST SYSTEM THAT IS |
| | IN COMPLIANCE. |
| | |
| | 2) PLEASE REVIEW SECTION C403.2.6 AND TABLE C403.2.6 |
| | FBC-14 ENERGY CONSERVATION AND SHOW COMPLIANCE AS |
| | APPLICABLE TO THE REQUIRED MAKEUP AIR FOR THE EXHAUST |
| | SYSTEM(S). |
| | 3) THE SUBMITTED ENERGY COMPLIANCE FORM 506-2010 IS |
| | OUTDATED FOR THE NEW 2014 FLORIDA BUILDING CODE CYCLE. |
| | PLEASE UPDATE THE SOFTWARE AND SUBMIT A VALID UP TO |
| | DATE PRINTOUT. |
| | |
| | AS THE SUBMITTED PLANS ARE INCOMPLETE, A THOROUGH |
| | REVIEW CANNOT BE ACCOMPLISHED AT THIS TIME. |
| | PLEASE NOTE THAT ADDITIONAL COMMENTS MAY FOLLOW AFTER |
| | THE REVISED PLANS HAVE BEEN SUBMITTED FOR REVIEW. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |