| Plan Review Notes For Permit 15080125 |
| Permit Number |
15080125 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-05 17:37:59 | RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC-5TH EDITION (2014) | | | | | | 1- PROVIDE FASTENER WITHDRAWAL TEST (TAS 105 OR ANSI | | | /SPRI FX-1) AS REQUIRED BY NOTE #9 OF FLORIDA PRODUCT | | | APPROVAL FL1046-R7 SUBMITTED. PROVIDE 2 COPIES WITH | | | ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY | | | CHAPTER 471 F.S. | | | | | | 2- BASED ON THE RESULTS OF THE FASTENER WITHDRAWAL TEST | | | REQUIRED BY ITEM #1 ABOVE, PROVIDE SIGNED AND SEALED | | | RAS 117 (OR FM LPDS 1-29) AS REQUIRED BY NOTE #7 OF | | | FLORIDA PRODUCT APPROVAL FL1046-R7 SUBMITTED. PROVIDE 2 | | | COPIES WITH ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS | | | REQUIRED BY CHAPTER 471 F.S. | | | | | | NOTE: ANY ROOF A/C EQUIPMENT REMOVAL REQUIRES SEPARATE | | | PERMIT. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] | | | | | | | | | |
|