| Plan Review Notes For Permit 15080124 |
| Permit Number |
15080124 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-11 14:01:53 | 8/11/15 - SPOKE W/CONTRACTOR WHO CONFIRMED THAT THIS IS | | | NOT AN INDEPENDENT SYSTEM; THUS THE CIRCULATION IS VIA | | | THE EXISTING POOL PUMP. | | 2015-08-07 11:19:08 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | IF THIS IS AN INDEPENDENT SYSTEM. | | | | | | 1. YOU SHALL SUBMIT AN ELECTRICAL DRAWING FOR YOUR | | | WATER CIRCULATION SYSTEM THROUGH THE SOLAR COLLECTOR. | | | 2. THIS CIRCULATION WATER PUMP SHALL COMPLY WITH ALL | | | 2011 NEC REQUIREMENTS, SPECIFICALLY THOSE OF SECTION | | | 680. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|