| 2015-09-23 14:38:30 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | 1- BUILDING IS LOCATED IN FLOOD ZONE A5 WITH A BASE |
| | FLOOD ELEVATION OF 7'-0". ACCORDING TO ELEVATION |
| | CERTIFICATE ON CITY RECORDS THE FINISH FLOOR ELEVATION |
| | OF THE GARAGE IS 6.6'. THE FINISHED FLOOR ELEVATION |
| | NEEDS TO BE AT LEAST 6" ABOVE THE BASED FLOOR ELEVATION |
| | (7'-6"MIN.) OR THE CONSTRUCTION OF THE NEW ADDITION |
| | NEEDS TO COMPLY WITH ALL THE REQUIREMENTS OF SEC. R322 |
| | OF FBC-RESIDENTIAL, 5TH EDITION (2014). COORDINATE WITH |
| | ITEM #3(C) AND #3(D) BELOW. |
| | |
| | 2- SHEET A-1: |
| | A) NEED TO SPECIFY CARBON MONOXIDE ALARMS WITHIN 10' OF |
| | EACH SLEEPING ROOM AS REQUIRED BY SEC. R315 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | B) REVISE THE GENERAL NOTES: REFERENCE THE CURRENT CODE |
| | IN EFFECT 2014 NOT 2010. CHAPTER 553 F.S. |
| | |
| | C) SPECIFY FLOOD RESISTANT MATERIALS AS REQUIRED BY |
| | SEC. R322.1.8. |
| | |
| | D) PROVIDE COMPLETE INFORMATION FOR THE FLOOD VENTS |
| | SHOWING COMPLIANCE WITH SEC. R322.2.2. CHECK REQUIRED |
| | NUMBER OF VENTS PER SIDE, LOCATION AND SIZE OF VENTS |
| | REQUIRED. NOTE: COORDINATE WITH FLOOD VENT PRODUCT |
| | APPROVAL. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR FLOOD VENTS. NOTE: COORDINATE |
| | WITH ITEM #3(D) ABOVE. |
| | |
| | 4- DESIGNER OF RECORD TO APPROVE FLOOD VENTS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. PLEASE |
| | PLACE REVIEW STAMP ON THE COVER OF THE PRODUCT APPROVAL |
| | NOT ON THE BACK. THIS WILL FACILITATE THE SCANNING OF |
| | ALL DOCUMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| | SUBMIT OLD COPIES FOR REFERENCE. |
| | |