| Notes |
| Date |
Text |
| 2015-08-20 17:45:25 | HAVING FIRST BEEN APPROVED BY ZONING, I CAN APPROVED | | | THE PERMIT WITH THE FOLLOWING PROVISOS | | | PROVISOS FOR PERMIT 15080090 | | | 1. ALL REPLACEMENT RECEPTACLES SHALL COMPLY WITH NEC | | | 406.4 (D)(1) ? (D)(4) | | | 2. OUTLET SPACING AS REFLECTED ON PLANS DOES NOT MEET | | | MINIMUM SPACING REQUIREMENTS MANDATED IN NEC 210.52. IF | | | ONLY REPLACING DEVICES W/O OPENING WALLS, OUTLETS MAY | | | REMAIN AS THEY ARE; OTHERWISE FOLLOW MINIMUM | | | REQUIREMENTS AS MARKED ON THE PLANS. | | | 3. ALL CEILING LUMINAIRE OUTLETS SHALL BE LISTED TO | | | SUPPORT 50 LB. PER NEC 314.27 | | | 4. PANEL ?B? FOR DETACHED STRUCTURE SHALL BE GROUNDED | | | AS INDICATED. | | | |
|