| Plan Review Notes For Permit 15080079 |
| Permit Number |
15080079 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-19 04:02:01 | 1) THE SUBMITTED PLANS ARE COPIES. PER FL. ADMIN. CODE | | | RULE 61G1-16.003 -PLANS, DOCUMENTS ETC. SHALL BE SIGNED | | | AND SEALED BY THE DESIGN PROFESSIONAL . | | | 2) THE PLANS SHALL BE DRAWN TO A MINIMUM OF 1/8 INCH | | | SCALE PER THE WPB AMEND. TO FBC SEC. 107.2.1.4. | | | 3) CLEARLY IDENTIFY THE AREAS ON THE PLANS WHERE THE | | | REMODEL WORK IS BEING DONE.IS IT THE ENTIRE FLOOR?ARE | | | ALL THE SHOWERS BEING REDONE:CLARIFY. | | | 4) INDICATE THE LEVEL OF WORK/WORK AREA PER | | | FBC-EEXISTING BUILDING CODE SEC.501.2. | | | 5) THE PLANS SHOW A LAUNDRY AREA. WILL THERE BE ANY | | | WRORK DONE IN THIS AREA? THERE IS ALSO GAS SHOWN IN | | | THIS AREA. ARE THERE ANY CHANGES BEING MADE TO THE GAS | | | SYSTEM? | | | 6) THE CONTRACT REFERS TO TWO SEPARATE BUILDINGS. | | | CLEARLY SHOW THIS ON THE PLANS AND THE PERMIT | | | APPLICATIONS. | | | 7) SUBMIT A SANITARY AND WATER RISER DIAGRAM TO REFLECT | | | ANY CHANGES BEING MADE TO THE PLUMBING SYSTEM. WPB | | | AMEND. TO FBC SEC | | | DUE TO THE VAGUE NATURE OF THE PLANS, A COMPREHENSIVE | | | REVIEW COULD NOT BE CONDUCTED AT THIS TIME AND | | | THEREFORE, ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED ON SUBSEQUENT REVIEWS. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|