2015-09-26 07:40:301) I AM CHALLENGING THE VALUE OF THE PROJECT. THE COST
 OF THE WASHERS AND DRYERS SHALL BE INCLUDED IN THE
 VALUATION ALONG WITH ALL OTHER NEW EQUIPMENT AND LABOR.
 WPB AMEND. TO FBC SEC. 109.3.SUBMIT A DETAILED,
 QUANTITY ESTIMATE AND/OR BONA FIDE SIGNED CONTRACT FOR
 THE TOTAL COSTOF THIS PROJECT FOR REVIEW. 2ND REQUEST.
 2) CLEARLY IDENTIFY AND SHOW THE LOCATION OF ALL
 STEP-DOWN GAS REGULATORS FOR THE GAS SYSTEM. SINCE THIS
 IS BEING DESIGNED AS A 2 PSI GAS SYSTEM THE GAS PIPING
 SHALL EITHER HAVE STEP-DOWN REGULATORS LOCATED AT EACH
 APPLIANCE OR THE REGULATORS SHALL BE LOCATED TO MEET
 THE GAS CODE FOR PIPE SIZING. THE ONE REGULATOR
 DOWNSTREAM OF THE GAS METER IS NOT SUFFICIENT.THE
 SYMBOLS ON EACH GAS SUPPLY UPSTREAM OF THE GAS COCK ARE
 NOT IDENTIFIED SO IT IS DIFFICULT TO ESTABLISH
 COMPLIANCE WITH THE GAS CODE.2ND REQUEST.
 3) THE WALL AROUND THE DRYERS IN THE SOUTH AREA IS NOT
 AN EXISTING WALL. I SAW IT MYSELF AND IT WAS
 CONSTRUCTED OF NEW METAL STUDS AND DRYWALL. THIS SHALL
 BE INCLUDED IN THE SCOPE OF WORK AND VALUE FOR THIS
 PROJECT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR