| 2015-08-06 13:17:04 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15080078 | | | 8/6/15 | | | | | | 1) REFER TO SECTION 501 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE THE LEVEL OF ALTERATION ON THE PLAN (1, 2, | | | OR 3). | | | 2) REFER TO SECTION 809.1 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE A VENTILATION CALCULATION IN COMPLIANCE | | | WITH TABLE 403.3 FBC--14 MECHANICAL. LAUNDRIES ARE | | | REQUIRED TO HAVE FRESH AIR PROVIDED MECHANICALLY AT A | | | RATE OF 7.5 CFM PER OCCUPANT AND 0.06 CFM'S PER SQ. FT. | | | PROVIDE A TABLE ON THE PLAN SHOWING THE REQUIRED AIR | | | AND THE PROVIDED, AND INDICATE HOW THE AIR IS BEING | | | PROVIDED- VIA THE EXISTING SYSTEM, MODIFIED SYSTEM, OR | | | NEW SYSTEM? | | | 3) PROVIDE THE MAKE AND MODEL NUMBERS OF THE NEW GAS | | | DRYERS ON THE PLAN, AND SUBMIT MANUFACTURER'S | | | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS REVIEWED | | | AND APPROVED BY THE DESIGN PROFESSIONAL OF RECORD- | | | REFER TO SECTION 613.1 FBC-14 FUEL GAS. | | | 4) PLEASE NOTE THAT ADDITIONAL COMMENTS MAY FOLLOW | | | AFTER THE DRYER SPECS HAVE BEEN SUBMITTED FOR REVIEW. | | | AS STATED BEFORE THE DESIGN PROFESSIONAL OF RECORD | | | SHALL REVIEW THE DOCUMENTS, AND VERIFY THAT THE | | | EXISTING MAKEUP AIR AND EXHAUST SYSTEMS ARE ADEQUATELY | | | SIZED AND MEET THE SPECIFIED CRITERIA FOR USE WITH THE | | | NEW DRYERS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|