Plan Review Notes
Plan Review Notes For Permit 15080078
Permit Number 15080078
Review Stop B
Sequence Number 1
Notes
Date Text
2015-08-21 11:34:43 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT:15080078
 ADD: 4209 LAKE AVE.
 CONT: BRITE FUTURE PLUMBING
 TEL: (954)577-3651
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. AUGUST 21/ 2015
 ACTION: DENIED
  
 1) THE ARCHITECTURAL, MECH. ELEC. & PLUMB. SHEETS SHOW
 THE DESIGNER OF RECORD AS EDWARD J. KRANZ, P. E. #
 49453. NOTE THE PLANS ARE NOT SIGNED NOR SEALED.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009
 (2)(A) EVERY SHEET OF PLANS AND PRINTS WHICH MUST BE
 SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL
 BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
  
 2) IN REVIEWING THE PLUMBING COMMENTS AND THE PLUMBING
 PLAN REVIEWER GOING TO THE SITE FOUND WORK COMPLETED
 WITHOUT A PERMIT. PLUMBING COMMENT # 23 INDICATES ON
 THE SOUTHEAST CORNER OF THE TENANT SPACE THE SOUTH WALL
 A STOREFRONT DOOR WAS REMOVED AND REPLACED WITH A
 STOREFRONT GLASS PANEL. PALM BEACH COUNTY PICTOMETRY/
 BING STILL SHOWS A STOREFRONT DOOR IN THE LOCATION OF
 THE NEW STOREFRONT GLASS PANEL.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (B) WINDOWS
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) PLEASE PROVIDE THE WIND DESIGN CRITERIA: 2014 FBC-B
 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF
 ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 5) SHEET M-1 SHOWS DRYER EXHAUST DETAILS WITH A ROOF
 TOP ENCLOSURE BUT HTERE IS NO DESIGN CRITERIA FOR THE
 STRUCTURE HOW IT WILL MEET THE ROOF TOP WIND NOR IS
 THERE INFORMATION AS TO HOW IT WILL BE ANCHORED TO THE
 ROOF FRAMING MEMBERS TO RESIST THE MOMENT OF OVER
 TURNING ? 107.2.1.3. ADDITIONAL INFORMATION IS
 REQUIRED. FBC-B 1609.8 ROOFTOP STRUCTURES AND
 EQUIPMENT.
  
 6) NEITHER THE MECHANICAL OR STRUCTURAL SHEETS SHOW HOW
 THE EXHAUST VENTS ARE TO BE CUT THROUGH THE ROOF AND
 ANCHORED TO RESIST THE MOMENT OF OVER TURNING.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 7) THE VALUE STATED ON THE PERMIT APPLICATION IS
 EMBARRASSING LOW!!!! PLEASE CORRECT VALUE. 108.3*
 BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  