| 2015-08-19 09:15:05 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15080077 |
| | 8/19/15 |
| | |
| | 1) A COMPLETE REVIEW OF THE PROPOSED DAY CARE OCCUPANCY |
| | CANNOT BE ACCOMPLISHED UNTIL THE PLANS HAVE BEEN |
| | REVISED IN ACCORDANCE WITH BUILDING PLAN REVIEW |
| | COMMENTS (JWITMER- 8/8/15). PLEASE SUBMIT CORRECTED |
| | PLANS FOR REVIEW. |
| | 2) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING |
| | CODE AND PROVIDE VENTILATION CALCULATIONS FOR ALL |
| | PROPOSED ROOMS AND SPACES IN ACCORDANCE WITH TABLE |
| | 403.3 FBC-14 MECHANICAL. PROVIDE A SCHEDULE ON THE PLAN |
| | INDICATING THE REQUIRED AMOUNT CFM'S OF OUTSIDE AIR, |
| | AND THE AMOUNT OF CFM'S BEING PROVIDED BY THE EXISTING |
| | SYSTEM(S). REVISE THE PLANS TRO SHOW ANY REQUIRED |
| | ALTERATIONS OR MODIFICATIONS TO THE EXISTING SYSTEM(S) |
| | TO ACCOMODATE THE NEW OCCUPANCY. |
| | 3.A) REFER TO SECTION 466.7 FBC-14 BUILDING: DETECTION |
| | AND ALARM SYSTEMS. |
| | DAY CARE OCCUPANCIES SHALL BE PROVIDED WITH A FIRE |
| | ALARM SYSTEM IN ACCORDANCE WITH SECTION 907 AND THIS |
| | SECTION. |
| | 3.B) REFER TO SECTION 466.7.2 DETECTION. |
| | A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN |
| | ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN |
| | EACH STORY IN FRONT OF DOORS TO THE STAIRWAYS AND IN |
| | THE CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAY CARE |
| | OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN |
| | LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY |
| | CARE OCCUPANCY. |
| | |
| | PLEASE NOTE THAT MEETING COMPLIANCE WITH THE ABOVE |
| | SECTIONS WILL REQUIRE ANY NEW OR EXISTING DUCT SMOKE |
| | DETECTORS, FIRE DAMPERS, OR SMOKE DAMPERS TO BE LINKED |
| | WITH THE ALARM SYSTEM. |
| | 4) PLEASE PROVIDE A RESPONSE NARRATIVE TO ALL BUILDING |
| | DEPARTMENT COMMENTS FROM THE DESIGN PROFESSIONAL OF |
| | RECORD. |
| | |