| Plan Review Notes For Permit 15080077 |
| Permit Number |
15080077 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-03 14:41:02 | EXTERIOR DETAILS NOT PROVIDED, NO EVALUATION PERFORMED. | | | INCORRECT CODES ARE CITED, CURRENT EDITION ISS THE 5TH | | | EDITION FBC AND 2011NEC | | | DRAWING DOES NOT PROVIDE DETAILS OF WIRING METHODS USED | | | PLEASE PROVIDE ALL FIRE RATED ASSEMBLY NUMBERS AND | | | LOCATIONS SO A REVIEW OF THE MATERIALS USED CAN BE | | | EVALUATED | | | A REVIEW OF THE CHANGE OF OCCUPANCY FOR CURRENT CODE | | | REQUIREMENTS, INCLUDING WIRING METHODS, CANNOT BE | | | PERFORMED WITHOUT ALL OF THE INFORMATION | | | FIRE ALARM SYSTEM SPECIFICATIONS, LOCATIONS AND DRAWING | | | NEED TO BE SUPPLIED FOR COMPLIANCE REVIEW | | | INDICATE LOCATION, STYLE AND TYPE OF EXIT LIGHTS | | | INSTALLED | | | EMERGENCY LIGHTING PLAN DOES NOT APPEAR TO BE INCLUDED | | | UNABLE TO PERFORM A COMPLETE REVIEW AT THIS TIME DUE TO | | | A LACK OF INFORMATION |
|