| Plan Review Notes For Permit 15080059 |
| Permit Number |
15080059 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-04 15:34:59 | 1ST REVIEW: FBC 2010/2008 NEC | | | | | | THE PROVIDED LOAD CALCULATION INDICATES A CALCULATED | | | DEMAND OF 222 AMPS YET ONLY A 200AMP PANEL IS PROVIDED. | | | | | | ALSO PER FBC 107 PROVIDE A PANEL SCHEULE FOR THE 60AMP | | | SUB PANEL AND INFORMATION AS TO WHAT IT IS FEEDING. | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|