2015-08-03 15:17:461ST REVIEW: FBC 2014 BUILDING
 8/3/15
  
 1) THE SUBMITTED FLORIDA PRODUCT APPROVAL FOR THE
 CERTAINTEED ROOF UNDERLAYMENT IS THE OUTDATED 2010
 VERSION. PROVIDE TWO COPIES OF THE CURRENT 2014 PRODUCT
 APPROVAL, AND PLEASE CIRCLE, HIGHLIGHT, OR OTHERWISE
 MARK ALL NOTES, DETAILS, AND TABLES APPLICABLE TO THE
 PROPOSED INSTALLATION.
 2) THE SUBMITTED NOA FOR THE JOHNS MANVILLE MODIFIED
 BITUMEN IS INCOMPLETE: PLEASE SUBMIT THE SHEET THAT
 INDICATES THE ACTUAL SYSTEM TO BE INSTALLED, AND THE
 SHEET LISTING THE LIMITATIONS OF USE. PLEASE NOTE: A)
 ENGINEERING MAY BE REQUIRED PER LIMITATION #7 ON THE
 NOA. B) THE CERTAINTEED UNDERLAYMENT CANNOT BE USED
 WITH THE JOHNS MANVILLE ROOFING SYSTEM UNLESS IT IS
 SPECIFICALLY REFERENCED IN THE MANSVILLE NOA.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER