| 2015-09-22 17:48:08 | ****PROVISOS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | PROVISO, FLOOR PLANS NOT REVIEWED AT THIS TIME. |
| | |
| | PROVISO, PERMIT IS ISSUED AT CONTRACTOR'S RISK (PHASED |
| | CONSTRUCTION FBC 105.13). |
| | |
| | PROVISO, SEPARATE PERMITS REQUIRED FOR LANDSCAPING, |
| | PARKING LOT STRIPING AND LIGHTING, SIGNS, SEPARATE |
| | STRUCTURES. |
| | |
| | PROVISO, ON THE PLAN, REFERENCE IS MADE TO EIFS AND |
| | POLYSTYRENE. NOTE THAT THIS IS A TYPE II NONCOMBUSTIBLE |
| | BUILDING AND ALL MATERIALS WILL BE IN COMPLIANCE WITH |
| | FBC 602.2, 603. ANY EXCEPTIONS SHOULD BE INCORPORATED |
| | INTO THE PLAN (WHEN BUILDING PLANS ARE SUBMITTED). |
| | |
| | PROVISO, STAIRS NOT INCLUDED IN SCOPE. STRUCTURAL |
| | SHEETS WERE SUBMITTED 2ND REVIEW BUT DIMENSIONS TO SHOW |
| | COMPLIANCE WITH FBC 1009 WERE NOT PROVIDED. SUBMIT A |
| | REVISION TO INCORPORATE THIS INTO SCOPE. |
| | |
| | PROVISO, POLYSTYRENE IS SPECIFIED (SEE DETAIL 7 S415 |
| | AND OTHER LOCATIONS). PER ARCHITECT, THIS IS NOT |
| | INCLUDED IN THE SCOPE OF THIS PERMIT. FBC 602, 603 |
| | PROVIDE PRODUCT DATA REGARDING COMBUSTIBILITY WHEN |
| | SUBMITTING THE FULL BUILDING PERMIT. |
| | |
| | PROVISO, SPECIFICATION PACKAGE NOT REVIEWED. PLANS ARE |
| | TO DEMONSTRATE CODE COMPLIANCE INDEPENDENTLY OF THIS |
| | DOCUMENT. |
| | |
| | ADVISORY ONLY, PRODUCT APPROVALS WILL BE REQUIRED FOR |
| | COMPONENTS AND CLADDING. THEY ARE REQUIRED TO BE |
| | SUBMITTED, AFTER DESIGNER OF RECORD REVIEW, PRIOR TO |
| | INSTALLATION. |
| | |
| | |