2015-09-22 17:48:08****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROVISO, FLOOR PLANS NOT REVIEWED AT THIS TIME.
  
 PROVISO, PERMIT IS ISSUED AT CONTRACTOR'S RISK (PHASED
 CONSTRUCTION FBC 105.13).
  
 PROVISO, SEPARATE PERMITS REQUIRED FOR LANDSCAPING,
 PARKING LOT STRIPING AND LIGHTING, SIGNS, SEPARATE
 STRUCTURES.
  
 PROVISO, ON THE PLAN, REFERENCE IS MADE TO EIFS AND
 POLYSTYRENE. NOTE THAT THIS IS A TYPE II NONCOMBUSTIBLE
 BUILDING AND ALL MATERIALS WILL BE IN COMPLIANCE WITH
 FBC 602.2, 603. ANY EXCEPTIONS SHOULD BE INCORPORATED
 INTO THE PLAN (WHEN BUILDING PLANS ARE SUBMITTED).
  
 PROVISO, STAIRS NOT INCLUDED IN SCOPE. STRUCTURAL
 SHEETS WERE SUBMITTED 2ND REVIEW BUT DIMENSIONS TO SHOW
 COMPLIANCE WITH FBC 1009 WERE NOT PROVIDED. SUBMIT A
 REVISION TO INCORPORATE THIS INTO SCOPE.
  
 PROVISO, POLYSTYRENE IS SPECIFIED (SEE DETAIL 7 S415
 AND OTHER LOCATIONS). PER ARCHITECT, THIS IS NOT
 INCLUDED IN THE SCOPE OF THIS PERMIT. FBC 602, 603
 PROVIDE PRODUCT DATA REGARDING COMBUSTIBILITY WHEN
 SUBMITTING THE FULL BUILDING PERMIT.
  
 PROVISO, SPECIFICATION PACKAGE NOT REVIEWED. PLANS ARE
 TO DEMONSTRATE CODE COMPLIANCE INDEPENDENTLY OF THIS
 DOCUMENT.
  
 ADVISORY ONLY, PRODUCT APPROVALS WILL BE REQUIRED FOR
 COMPONENTS AND CLADDING. THEY ARE REQUIRED TO BE
 SUBMITTED, AFTER DESIGNER OF RECORD REVIEW, PRIOR TO
 INSTALLATION.
  
  