Plan Review Notes
Plan Review Notes For Permit 15080008
Permit Number 15080008
Review Stop B
Sequence Number 1
Notes
Date Text
2015-08-19 09:33:14****CORRECTIONS****
 REVISED 8/28/15
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE THRESHOLD REVIEW. THRESHOLD INSPECTION PLAN AND
 OTHER REQUESTED DOCUMENTS ARE TO BE APPROVED PRIOR TO
 PERMIT ISSUANCE.
  
 ALL PLANS PROVIDED BY ARCHITECT AND ENGINEER(S) ARE TO
 INCLUDE THE STATEMENT PER FLORIDA STATUTE 553.79(7)(D):
  
 THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT CONSISTENT WITH
 THE FLORIDA STATUTE REQUIREMENT FS 553.79(7)(D):
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER AND CHAPTER 633.
  
 2. SEE IMPACT REVIEW. BEFORE A PERMIT TO CONSTRUCT MAY
 BE ISSUED, AN IMPACT FEE ASSESSMENT BY PALM BEACH
 COUNTY IS REQUIRED. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 PROVIDED. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3. SEE FS471, FS 481. A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED TO PRACTICE ARCHITECTURE OR ENGINEERING
 THROUGH A COMPANY.
  
 COMMENT FOR ALL DESIGN PROFESSIONALS EXCEPT KIMLEY HORN
 AND CODE CONSULTANTS; THE CERTIFICATE OF AUTHORIZATION
 IS TO BE ON EACH SHEET (INCORPORATED INTO THE TITLE
 BLOCK), FAC61G15 23.002, FS471, FS481.
  
 COMMENT FOR HOBBS & BLACK; SEND LICENSE NUMBER WHEN
 AVAILABLE (SEE PROVISO).
  
 COMMENT FOR E&S CONSTRUCTION ENGINEERING (PLUMBING
 ENGINEER), SEND LICENSE NUMBER WHEN AVAILABLE (SEE
 PROVISO).
  
 THIS COMMENT WAS SENT TO WHITING TURNER AND RH VIA
 EMAIL ON 8.19.15.
  
 4. AT THE LOCATION OF THE SEAL, ALL SHEETS, THIS AREA
 IS NOTED ON THE PLAN AS A CONSULTANT. PLEASE REMOVE
 THIS LANGUAGE AS IT APPEARS THAT THE PLANS PROVIDED
 HAVE BEEN DESIGNED BY THE DESIGN PROFESSIONALS TAKING
 RESPONSIBILITY FOR THE PLANS, FS471, FS481. OR, CLARIFY
 USE OF THE WORD CONSULTANT ON THE PLANS AS APPLICABLE
 TO THIS STRUCTURE.
  
 5. GOVERNING CODE CHANGED TO FLORIDA BUILDING CODE 5TH
 EDITION (OR FBC 2014) ON JUNE 31, 2015; REVISE BUILDING
 CODE DATA (SHEET A003), STRUCTURAL CALCS, S002, AND
 OTHER SHEETS AS APPLICABLE. SHEET S102, NOTES INCLUDES
 REFERENCES TO FBC 2012, PLEASE REVISE.
  
 6. FOR A FOUNDATION PERMIT, ENOUGH INFORMATION TO
 DEMONSTRATE CODE COMPLIANCE REGARDING THE PROPOSED
 BUILDING IS REQUIRED. A003 IS NOTED FOR REFERENCE ONLY,
 BUT THIS SHEET IS REQUIRED, FBC TABLE 503. A050 SHOWS
 THE LOCATION OF THE PROPOSED CONSTRUCTION IN RELATION
 TO THE LOT LINES, FBC TABLE 602. THESE TWO SHEETS ARE
 REQUIRED FOR A FOUNDATION AND STRUCTURE PERMIT.
  
 7. SEE STRUCTURAL CALCS. THIS DOCUMENT REFERENCES ACI
 318 08; THE STANDARD SHOULD BE ACI 318 11. AISC 360
 SHOULD REFERENCE 2010 (NOT 2005), SEE FBC CHAPTER 35.
 REVISE ANY OTHER STANDARDS AS APPLICABLE.
  
 8. REVISED TO BE A PROVISO ITEM (POLYSTYRENE NOT
 INCLUDED IN SCOPE OF THIS PERMIT).
  
 PROVISO ITEMS (INFORMATIONAL OR TO BE ADDRESSED AT A
 FUTURE DATE)
  
 PROVISO, FLOOR PLANS NOT REVIEWED AT THIS TIME.
  
 PROVISO, PERMIT IS ISSUED AT CONTRACTOR'S RISK (PHASED
 CONSTRUCTION FBC 105.13).
  
 PROVISO, SEPARATE PERMITS REQUIRED FOR LANDSCAPING,
 PARKING LOT STRIPING AND LIGHTING, SIGNS, SEPARATE
 STRUCTURES.
  
 PROVISO, ON THE PLAN, REFERENCE IS MADE TO EIFS AND
 POLYSTYRENE. NOTE THAT THIS IS A TYPE II NONCOMBUSTIBLE
 BUILDING AND ALL MATERIALS WILL BE IN COMPLIANCE WITH
 FBC 602.2, 603. ANY EXCEPTIONS SHOULD BE INCORPORATED
 INTO THE PLAN (WHEN BUILDING PLANS ARE SUBMITTED).
  
 PROVISO, PROVIDE ARCHITECT BUSINESS LICENSE NUMBER WHEN
 AVAILABLE; ISSUED AT CONTRACTOR'S RISK AND REQUIRED
 PRIOR TO C.O.
 PROVISO, PROVIDE PLUMBING ENGINEER'S BUSINESS LICENSE
 NUMBER WHEN AVAILABLE; ISSUED AT CONTRACTOR'S RISK AND
 REQUIRED PRIOR TO C.O.
  
 PROVISO, POLYSTYRENE IS SPECIFIED (SEE DETAIL 7 S415
 AND OTHER LOCATIONS). PER ARCHITECT, THIS IS NOT
 INCLUDED IN THE SCOPE OF THIS PERMIT. FBC 602, 603
 PROVIDE PRODUCT DATA REGARDING COMBUSTIBILITY WHEN
 SUBMITTING THE FULL BUILDING PERMIT.
  
 ADVISORY ONLY, PRODUCT APPROVALS WILL BE REQUIRED FOR
 COMPONENTS AND CLADDING. THEY ARE REQUIRED TO BE
 SUBMITTED, AFTER DESIGNER OF RECORD REVIEW, PRIOR TO
 INSTALLATION.
  
  