| Date |
Text |
| 2015-08-19 09:33:14 | ****CORRECTIONS**** |
| | REVISED 8/28/15 |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. SEE THRESHOLD REVIEW. THRESHOLD INSPECTION PLAN AND |
| | OTHER REQUESTED DOCUMENTS ARE TO BE APPROVED PRIOR TO |
| | PERMIT ISSUANCE. |
| | |
| | ALL PLANS PROVIDED BY ARCHITECT AND ENGINEER(S) ARE TO |
| | INCLUDE THE STATEMENT PER FLORIDA STATUTE 553.79(7)(D): |
| | |
| | THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B. AMENDMENT |
| | 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH ARE |
| | REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR |
| | ENGINEER OF RECORD CONTAIN A STATEMENT CONSISTENT WITH |
| | THE FLORIDA STATUTE REQUIREMENT FS 553.79(7)(D): |
| | ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE |
| | SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS CHAPTER AND CHAPTER 633. |
| | |
| | 2. SEE IMPACT REVIEW. BEFORE A PERMIT TO CONSTRUCT MAY |
| | BE ISSUED, AN IMPACT FEE ASSESSMENT BY PALM BEACH |
| | COUNTY IS REQUIRED. THE ACTUAL PERMIT SET OF PLANS MUST |
| | BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID |
| | PROVIDED. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3. SEE FS471, FS 481. A CERTIFICATE OF AUTHORIZATION IS |
| | REQUIRED TO PRACTICE ARCHITECTURE OR ENGINEERING |
| | THROUGH A COMPANY. |
| | |
| | COMMENT FOR ALL DESIGN PROFESSIONALS EXCEPT KIMLEY HORN |
| | AND CODE CONSULTANTS; THE CERTIFICATE OF AUTHORIZATION |
| | IS TO BE ON EACH SHEET (INCORPORATED INTO THE TITLE |
| | BLOCK), FAC61G15 23.002, FS471, FS481. |
| | |
| | COMMENT FOR HOBBS & BLACK; SEND LICENSE NUMBER WHEN |
| | AVAILABLE (SEE PROVISO). |
| | |
| | COMMENT FOR E&S CONSTRUCTION ENGINEERING (PLUMBING |
| | ENGINEER), SEND LICENSE NUMBER WHEN AVAILABLE (SEE |
| | PROVISO). |
| | |
| | THIS COMMENT WAS SENT TO WHITING TURNER AND RH VIA |
| | EMAIL ON 8.19.15. |
| | |
| | 4. AT THE LOCATION OF THE SEAL, ALL SHEETS, THIS AREA |
| | IS NOTED ON THE PLAN AS A CONSULTANT. PLEASE REMOVE |
| | THIS LANGUAGE AS IT APPEARS THAT THE PLANS PROVIDED |
| | HAVE BEEN DESIGNED BY THE DESIGN PROFESSIONALS TAKING |
| | RESPONSIBILITY FOR THE PLANS, FS471, FS481. OR, CLARIFY |
| | USE OF THE WORD CONSULTANT ON THE PLANS AS APPLICABLE |
| | TO THIS STRUCTURE. |
| | |
| | 5. GOVERNING CODE CHANGED TO FLORIDA BUILDING CODE 5TH |
| | EDITION (OR FBC 2014) ON JUNE 31, 2015; REVISE BUILDING |
| | CODE DATA (SHEET A003), STRUCTURAL CALCS, S002, AND |
| | OTHER SHEETS AS APPLICABLE. SHEET S102, NOTES INCLUDES |
| | REFERENCES TO FBC 2012, PLEASE REVISE. |
| | |
| | 6. FOR A FOUNDATION PERMIT, ENOUGH INFORMATION TO |
| | DEMONSTRATE CODE COMPLIANCE REGARDING THE PROPOSED |
| | BUILDING IS REQUIRED. A003 IS NOTED FOR REFERENCE ONLY, |
| | BUT THIS SHEET IS REQUIRED, FBC TABLE 503. A050 SHOWS |
| | THE LOCATION OF THE PROPOSED CONSTRUCTION IN RELATION |
| | TO THE LOT LINES, FBC TABLE 602. THESE TWO SHEETS ARE |
| | REQUIRED FOR A FOUNDATION AND STRUCTURE PERMIT. |
| | |
| | 7. SEE STRUCTURAL CALCS. THIS DOCUMENT REFERENCES ACI |
| | 318 08; THE STANDARD SHOULD BE ACI 318 11. AISC 360 |
| | SHOULD REFERENCE 2010 (NOT 2005), SEE FBC CHAPTER 35. |
| | REVISE ANY OTHER STANDARDS AS APPLICABLE. |
| | |
| | 8. REVISED TO BE A PROVISO ITEM (POLYSTYRENE NOT |
| | INCLUDED IN SCOPE OF THIS PERMIT). |
| | |
| | PROVISO ITEMS (INFORMATIONAL OR TO BE ADDRESSED AT A |
| | FUTURE DATE) |
| | |
| | PROVISO, FLOOR PLANS NOT REVIEWED AT THIS TIME. |
| | |
| | PROVISO, PERMIT IS ISSUED AT CONTRACTOR'S RISK (PHASED |
| | CONSTRUCTION FBC 105.13). |
| | |
| | PROVISO, SEPARATE PERMITS REQUIRED FOR LANDSCAPING, |
| | PARKING LOT STRIPING AND LIGHTING, SIGNS, SEPARATE |
| | STRUCTURES. |
| | |
| | PROVISO, ON THE PLAN, REFERENCE IS MADE TO EIFS AND |
| | POLYSTYRENE. NOTE THAT THIS IS A TYPE II NONCOMBUSTIBLE |
| | BUILDING AND ALL MATERIALS WILL BE IN COMPLIANCE WITH |
| | FBC 602.2, 603. ANY EXCEPTIONS SHOULD BE INCORPORATED |
| | INTO THE PLAN (WHEN BUILDING PLANS ARE SUBMITTED). |
| | |
| | PROVISO, PROVIDE ARCHITECT BUSINESS LICENSE NUMBER WHEN |
| | AVAILABLE; ISSUED AT CONTRACTOR'S RISK AND REQUIRED |
| | PRIOR TO C.O. |
| | PROVISO, PROVIDE PLUMBING ENGINEER'S BUSINESS LICENSE |
| | NUMBER WHEN AVAILABLE; ISSUED AT CONTRACTOR'S RISK AND |
| | REQUIRED PRIOR TO C.O. |
| | |
| | PROVISO, POLYSTYRENE IS SPECIFIED (SEE DETAIL 7 S415 |
| | AND OTHER LOCATIONS). PER ARCHITECT, THIS IS NOT |
| | INCLUDED IN THE SCOPE OF THIS PERMIT. FBC 602, 603 |
| | PROVIDE PRODUCT DATA REGARDING COMBUSTIBILITY WHEN |
| | SUBMITTING THE FULL BUILDING PERMIT. |
| | |
| | ADVISORY ONLY, PRODUCT APPROVALS WILL BE REQUIRED FOR |
| | COMPONENTS AND CLADDING. THEY ARE REQUIRED TO BE |
| | SUBMITTED, AFTER DESIGNER OF RECORD REVIEW, PRIOR TO |
| | INSTALLATION. |
| | |
| | |