| Plan Review Notes For Permit 15080007 |
| Permit Number |
15080007 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-14 12:59:31 | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | 561-805-6711 | | | [email protected] | | | | | | COMMENTS: | | | 1. SHEET A-8 RESTROOM DETAIL 1-2 SHOW INSTALLATION | | | HIGHT MEASURED TO THE TOP OF THE GRIPPING SURFACE. | | | TO COMPLY WITH FBC ACC SEC.609.4 | | | 2. SHEET P-2 PLEASE PROVIDE CALCULATION FOR SIZING OIL | | | SEPARATOR. | | | TO COMPLY WITH FBCP 10003.4.2.2 | | | 3. PLEASE PROVIDE INSTILLATION GUIDE FOR SCHIER MODEL | | | OS-75. | | | TO COMPLYWITH WPB AMENDMENTS TO FBC 2010 SEC 107.2.1.3 |
|