| Date |
Text |
| 2015-08-27 19:45:34 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | 1. CORRECT YOUR REFERENCED CODES AS FOLLOWS: |
| | A) FLORIDA FIRE PREVENTION CODE (FFPC) 2012 EDITION |
| | B) NFPA 1, 2012 EDITION |
| | C) NFPA 70, 2011 EDITION (NEC) |
| | D) NFPA 72, 2010 EDITION |
| | E) NFPA 101, 2012 EDITION |
| | F) FBC, 5TH EDITION 2014 (FLORIDA BLDG. CODE) |
| | 2. WHEN MAKING REFERENCES TO SPECIFIC CODE SECTIONS, |
| | MAKE IT COUNT. PLEASE HELP ME FIND SECTION 760.61 OF |
| | THE 2011 NEC. |
| | 3. AGAIN, I DON?T KNOW WHAT IS TO BE REPRESENTED IN |
| | CHAPTER 7 OF NFPA 72. PLEASE ASSIST. |
| | 4. THE FIRE STOPPING MATERIAL PROPOSED FOR THE CABLES |
| | PENETRATING GYPSUM (DRYWALL) WALLS IS UNACCEPTABLE. |
| | ACCORDING TO NOTE 2 THIS PRODUCT INDICATES THE USE OF |
| | ALUMINUM CONDUCTORS |
| | 5. YOUR SCOPE OF WORK AS INDICATED ON SHEET FA-01 FAILS |
| | TO INCLUDE ANY NOTIFICATION DEVICES. |
| | 6. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATIONS |
| | SHALL BE MOUNTED WITHIN 5? OF THE EXIT. RELOCATE THAT |
| | OF THE RECEPTION AREA ACCORDINGLY. |
| | 7. YOUR BATTERY CALC NUMBERS ARE INCORRECT, YET YOU |
| | ARRIVED AT THE CORRECT SUM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |