2015-08-10 08:05:131ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15071231
 8/10/15
  
 1) SHEET M-1: PROVIDE A SCOPE OF WORK OUTLINE ON THE
 PLAN CLARIFYING ALL PROPOSED ALTERATIONS TO THE
 EXISTING SYSTEMS.
 2) M-1: LABEL ALL DUCT WORK (MAIN TRUNKS AND BRANCHES)
 AS EITHER NEW, EXISTING, OR RELOCATED.
 3) M-1: PROVIDE AN AIR DISTRIBUTION SCHEDULE LISTING
 THE MAKES AND MODELS OF ALL COMPONENTS.
 4) M-1: REFER TO SECTION 505 FBC-10 MECHANICAL:
 INDICATE THE CFM CAPACITY OF THE EXHAUST HOOD AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE HOOD AND
 THE EXHAUST DUCTWORK. PLEASE NOTE THAT MAKEUP AIR MAY
 BE REQUIRED PER SECTION 505.2.
  