Plan Review Notes
Plan Review Notes For Permit 15071219
Permit Number 15071219
Review Stop B
Sequence Number 2
Notes
Date Text
2015-11-02 17:05:47BUILDING PLAN REVIEW
 REVISION: 15071219
 PERMIT: 14110788
 ADD: 418 25TH ST
 CONT: SOUTHERN COAST
 TEL: (561)584-8502
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE:MON. NOV. 02/ 2015
 ACTION: DENIED.
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
  
 1) THE SCOPE OF THE PROJECT HAS GREATLY INCREASE BUT
 THERE IS NO INCREASE IN VALUE. W P B ADMINISTRATIVE
 CODE 108.2 SCHEDULE OF PERMIT FEES. ON BUILDINGS,
 STRUCTURES, ELECTRICAL, GAS, MECHANICAL AND PLUMBING
 SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A FEE FOR
 EACH PERMIT SHALL BE PAID AS REQUIRED, IN ACCORDANCE
 WITH THE SCHEDULE ESTABLISHED BY THE APPLICABLE
 GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) PROVIO:. PRODUCT APPROVALS : 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, SWING & OVERHEAD DOORS. MISSING
 OVERHEAD DOOR. NO SHOP DRAWING STAMP OF APPROVAL FROM
 THE DESIGNER OF RECORD.
 (B) WINDOWS NO SHOP DRAWING STAMP OF APPROVAL FROM THE
 DESIGNER OF RECORD.
 (C) PANEL WALLS: STOREFRONTS,NO SHOP DRAWING STAMP OF
 APPROVAL FROM THE DESIGNER OF RECORD.
 (E) SHUTTERS (NOTE) THE 2ND FLOOR 1 HOUR FIRE RATED
 WINDOW WILL REQUIRE STORM SHUTTERS UNLESS THE WINDOW
 WAS TESTED AS A 1 HR. RATED WINDOW & LARGE MISSILE
 IMPACT TESTED WINDOW. MISSING SHUTTER PRODUCT APPROVAL.
 NO SHOP DRAWING STAMP OF APPROVAL FROM THE DESIGNER OF
 RECORD.
  
 3) PROVISO. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) COMPLIED. SHEET A-2 & A-4 NEW RESTROOMS 102 & 106
 WILL NEED TO SHOW COMPLIANCE WITH 2010
 FBC-ACCESSIBILITY CODE 604.3.1 SIZE. CLEARANCE AROUND A
 WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM
 MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES
 (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL.
  
 5) COMPLIED.
  
 6) COMPLIED. SHEET S-2 NOTE G-1 INDICATES THE
 STRUCTURAL DESGIN IS TO THE 2014 FBC-B. NOTE THIS IS A
 REVISION TO A 2010 FBC PLAN, PLEASE CORRECT.
  
 7) 2ND REQUEST!!!!!!!!!!!! WHEN RESUBMITTING PLANS
 PLEASE INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS
 & REPLACE ANY PAGES AS NECESSARY. THE PLANS NEED TO BE
 PULLED APART AND REASSEMBLED SO THE SHEETS ARE IN
 NUMERICAL ORDER!!!!!!!!!!
  
 107.2.1.4 QUALITY OF BUILDING PLANS. . THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  