| Plan Review Notes For Permit 15071219 |
| Permit Number |
15071219 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-01 05:20:21 | 1) THE MINIMUM WIDTH OF THE TOILET ROOMS SHALL BE 85 | | | INCHES IF BUILT PERFECT. 86 INCHES ALLOWS FOR | | | TOLERANCES. 2014 FBC-ACCESSIBILITY SECS.604.3 AND | | | 606.2. | | | 2) SHT. A-4 - ENLARGED TOILET ROOM SHOWS THE LAVATORY | | | ENCROACHING INTO THE CLEAR FLOOR SPACEE FOR THE WATER | | | CLOSET. THE LAVATORY CANNOT ENCROACH INTO THIS AREA. | | | 2014 FBC-ACCESSIBILITY SEC.604.3. | | | 3) SHOW THE MOUNTING HEIGHTS/DIMENSIONS OF ALL FIXTURES | | | AND ITEMS LOCATED IN THE TOILET ROOM. COMPLY WITH 2014 | | | FBC CHAPTS.2 & 6. | | | 4) SUBMIT WATER AND SANITARY RISERS FOR THE FIRST AND | | | SECOND FLOORS. FBC AMEND. TO FBC SEC. 107.3.5.1.3. | | | 5) SHOW ALL PIPE SIZES FOR THE SANITARY AND WATER | | | RISERS.WPB AMEND. TO FBC SEC. 107.2.1. | | | 6) SIZE ALL CONDENSATE LINES. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 7) SUBMIT A DETAIL FOR THE DRYWELL.WPB AMEND. TO FBC | | | SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|