Plan Review Notes
Plan Review Notes For Permit 15071219
Permit Number 15071219
Review Stop M
Sequence Number 1
Notes
Date Text
2015-08-28 10:35:03SKENNEDY'S DESK
2015-08-07 10:53:501ST REVIEW: FBC 2010 MECHANICAL
 REVISION PERMIT #15071219
 MASTER #14110778
 8/7/15
  
 1) THE REVISED PLANS INDICATE NEW CONDITIONED OFFICE
 SPACES ON THE FIRST FLOOR INCLUDING THE ADDTION OF A
 NEW 3TON AC SYSTEM: SUBMIT REVISED ENERGY AND AC LOAD
 CALCULATIONS.
 2) REFER TO SECTION 301.12 FBC-10 MECHANICAL AND
 PROVIDE ENGINEERED STRUCTURAL DETAILS FOR SUPPORT AND
 ATTACHMENT OF THE AC CONDENSERS AND ROOF STANDS TO THE
 ROOF STRUCTURE. PLEASE ALSO SUBMIT A VALID FL. PRODUCT
 APPROVAL OR MIAMI-DADE NOA FOR THE ROOF STANDS REVIEWED
 AND APPROVED BY THE DESIGN PROFESSIONAL OF RECORD.
 3) REFER TO SECTION 304.11: THE NEW CONDENSERS WILL
 REQUIRE GUARDS IF WITHIN 10 FT. OF THE ROOF EDGE,
 UNLESS THE EXISTING PARAPET WALL HEIGHT IS MINIMUM 42"
 ABOVE THE ROOF LEVEL.
 4) SUBMIT PRODUCT APPROVALS OR NOA'S FOR THE RUSKIN
 LOUVERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER