| Plan Review Notes For Permit 15071219 |
| Permit Number |
15071219 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-28 10:35:03 | SKENNEDY'S DESK | | 2015-08-07 10:53:50 | 1ST REVIEW: FBC 2010 MECHANICAL | | | REVISION PERMIT #15071219 | | | MASTER #14110778 | | | 8/7/15 | | | | | | 1) THE REVISED PLANS INDICATE NEW CONDITIONED OFFICE | | | SPACES ON THE FIRST FLOOR INCLUDING THE ADDTION OF A | | | NEW 3TON AC SYSTEM: SUBMIT REVISED ENERGY AND AC LOAD | | | CALCULATIONS. | | | 2) REFER TO SECTION 301.12 FBC-10 MECHANICAL AND | | | PROVIDE ENGINEERED STRUCTURAL DETAILS FOR SUPPORT AND | | | ATTACHMENT OF THE AC CONDENSERS AND ROOF STANDS TO THE | | | ROOF STRUCTURE. PLEASE ALSO SUBMIT A VALID FL. PRODUCT | | | APPROVAL OR MIAMI-DADE NOA FOR THE ROOF STANDS REVIEWED | | | AND APPROVED BY THE DESIGN PROFESSIONAL OF RECORD. | | | 3) REFER TO SECTION 304.11: THE NEW CONDENSERS WILL | | | REQUIRE GUARDS IF WITHIN 10 FT. OF THE ROOF EDGE, | | | UNLESS THE EXISTING PARAPET WALL HEIGHT IS MINIMUM 42" | | | ABOVE THE ROOF LEVEL. | | | 4) SUBMIT PRODUCT APPROVALS OR NOA'S FOR THE RUSKIN | | | LOUVERS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|