| 2015-08-06 12:31:00 | BUILDING PLAN REVIEW |
| | REVISION: 15071219 |
| | PERMIT: 14110788 |
| | ADD: 418 25TH ST |
| | CONT: SOUTHERN COAST |
| | TEL: (561)584-8502 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE:THURS. AUG.06/ 2015 |
| | ACTION: DENIED. |
| | |
| | 1) THE SCOPE OF THE PROJECT HAS GREATLY INCREASE BUT |
| | THERE IS NO INCREASE IN VALUE. W P B ADMINISTRATIVE |
| | CODE 108.2 SCHEDULE OF PERMIT FEES. ON BUILDINGS, |
| | STRUCTURES, ELECTRICAL, GAS, MECHANICAL AND PLUMBING |
| | SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A FEE FOR |
| | EACH PERMIT SHALL BE PAID AS REQUIRED, IN ACCORDANCE |
| | WITH THE SCHEDULE ESTABLISHED BY THE APPLICABLE |
| | GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) PRODUCT APPROVALS : 2010 FBC-B 1609.1.2 PROTECTION |
| | OF OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS, SWING & OVERHEAD DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, |
| | (E) SHUTTERS (NOTE) THE 2ND FLOOR 1 HOUR FIRE RATED |
| | WINDOW WILL REQUIRE STORM SHUTTERS UNLESS THE WINDOW |
| | WAS TESTED AS A 1 HR. RATED WINDOW & LARGE MISSILE |
| | IMPACT TESTED WINDOW. |
| | |
| | 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) SHEET A-2 & A-4 NEW RESTROOMS 102 & 106 WILL NEED TO |
| | SHOW COMPLIANCE WITH 2010 FBC-ACCESSIBILITY CODE |
| | 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE |
| | 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM |
| | THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | |
| | 5) SHEET A-4 DETAIL # 1 INDICATES NEW METAL LOUVERED |
| | AWNING, THERE HAS BEEN NO DESIGN CRITERIA SUBMITTED FOR |
| | WIND DESIGN. IS THIS AWNING A FOLDING TYPE, OR RIGID, |
| | TYPE OF MATERIAL IT IS TO BE METAL FRAME AND LOUVER? |
| | PLEASE ALSO PROVIDE WHERE THE PROPERTY LINE IS LOCATED |
| | IN REGUARDS TO THE BUILDING. |
| | |
| | 5A)FBC-B 3202.2.3 AWNINGS. |
| | THE VERTICAL CLEARANCE FROM THE PUBLIC RIGHT-OF-WAY TO |
| | THE LOWEST PART OF ANY AWNING, INCLUDING VALANCES, |
| | SHALL BE NOT LESS THAN 7 FEET (2134 MM). |
| | |
| | 5B) FBC-B 3202.3 ENCROACHMENTS 8 FEET OR MORE ABOVE |
| | GRADE. |
| | ENCROACHMENTS 8 FEET (2438 MM) OR MORE ABOVE GRADE |
| | SHALL COMPLY WITH SECTIONS 3202.3.1 THROUGH 3202.3.4. |
| | |
| | 5C) FBC-B 3105.4.2.2 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR MEMBRANE |
| | COVERED STRUCTURE DESIGNED WITH A PERMANENT OR |
| | NONREMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE |
| | FOLLOWING CRITERIA: |
| | 1. MINIMUM WIND SPEED VELOCITY AS REQUIRED IN CHAPTER |
| | 16, USING FIGURE 1609C. |
| | 2. EXPOSURE B, C OR D AS DEFINED IN CHAPTER 16. |
| | |
| | 6) SHEET S-2 NOTE G-1 INDICATES THE STRUCTURAL DESGIN |
| | IS TO THE 2014 FBC-B. NOTE THIS IS A REVISION TO A 2010 |
| | FBC PLAN, PLEASE CORRECT. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |