Plan Review Notes
Plan Review Notes For Permit 15071219
Permit Number 15071219
Review Stop B
Sequence Number 1
Notes
Date Text
2015-08-06 12:31:00BUILDING PLAN REVIEW
 REVISION: 15071219
 PERMIT: 14110788
 ADD: 418 25TH ST
 CONT: SOUTHERN COAST
 TEL: (561)584-8502
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:THURS. AUG.06/ 2015
 ACTION: DENIED.
  
 1) THE SCOPE OF THE PROJECT HAS GREATLY INCREASE BUT
 THERE IS NO INCREASE IN VALUE. W P B ADMINISTRATIVE
 CODE 108.2 SCHEDULE OF PERMIT FEES. ON BUILDINGS,
 STRUCTURES, ELECTRICAL, GAS, MECHANICAL AND PLUMBING
 SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A FEE FOR
 EACH PERMIT SHALL BE PAID AS REQUIRED, IN ACCORDANCE
 WITH THE SCHEDULE ESTABLISHED BY THE APPLICABLE
 GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) PRODUCT APPROVALS : 2010 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, SWING & OVERHEAD DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS,
 (E) SHUTTERS (NOTE) THE 2ND FLOOR 1 HOUR FIRE RATED
 WINDOW WILL REQUIRE STORM SHUTTERS UNLESS THE WINDOW
 WAS TESTED AS A 1 HR. RATED WINDOW & LARGE MISSILE
 IMPACT TESTED WINDOW.
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) SHEET A-2 & A-4 NEW RESTROOMS 102 & 106 WILL NEED TO
 SHOW COMPLIANCE WITH 2010 FBC-ACCESSIBILITY CODE
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 5) SHEET A-4 DETAIL # 1 INDICATES NEW METAL LOUVERED
 AWNING, THERE HAS BEEN NO DESIGN CRITERIA SUBMITTED FOR
 WIND DESIGN. IS THIS AWNING A FOLDING TYPE, OR RIGID,
 TYPE OF MATERIAL IT IS TO BE METAL FRAME AND LOUVER?
 PLEASE ALSO PROVIDE WHERE THE PROPERTY LINE IS LOCATED
 IN REGUARDS TO THE BUILDING.
  
 5A)FBC-B 3202.2.3 AWNINGS.
 THE VERTICAL CLEARANCE FROM THE PUBLIC RIGHT-OF-WAY TO
 THE LOWEST PART OF ANY AWNING, INCLUDING VALANCES,
 SHALL BE NOT LESS THAN 7 FEET (2134 MM).
  
 5B) FBC-B 3202.3 ENCROACHMENTS 8 FEET OR MORE ABOVE
 GRADE.
 ENCROACHMENTS 8 FEET (2438 MM) OR MORE ABOVE GRADE
 SHALL COMPLY WITH SECTIONS 3202.3.1 THROUGH 3202.3.4.
  
 5C) FBC-B 3105.4.2.2
 THE WIND DESIGN LOADS FOR ANY FABRIC OR MEMBRANE
 COVERED STRUCTURE DESIGNED WITH A PERMANENT OR
 NONREMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE
 FOLLOWING CRITERIA:
 1. MINIMUM WIND SPEED VELOCITY AS REQUIRED IN CHAPTER
 16, USING FIGURE 1609C.
 2. EXPOSURE B, C OR D AS DEFINED IN CHAPTER 16.
  
 6) SHEET S-2 NOTE G-1 INDICATES THE STRUCTURAL DESGIN
 IS TO THE 2014 FBC-B. NOTE THIS IS A REVISION TO A 2010
 FBC PLAN, PLEASE CORRECT.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  