| Plan Review Notes For Permit 15071214 |
| Permit Number |
15071214 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-03 13:40:52 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | REVISION DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE LETTER FROM THE ARCHITECT FOR THE GACO FIRESTOP2 | | | SPRAY FOAM INSULATION IS NOT ADEQUATE. THE ARCHITECT | | | NEEDS TO SPECIFY THE APPLIED THICKNESS OF THE | | | INSULATION AND WHERE IT WILL BE APPLIED (THE UNDERSIDE | | | OF ROOF SHEATHING IN ATTIC?). FBC 107.2.1 | | | | | | 2) THE APPROVED PLAN SHOWS R-30 BATT INSULATION AT THE | | | BOTTOM CORD OF THE TRUSSES AND A VENTED ATTIC WITH A | | | CONTINUOUS 4" SOFFIT VENT. WHEN THE AIR-IMPERMEABLE | | | INSTALLATION IS INSTALLED TO THE UNDERSIDE OF THE ROOF | | | SHEATHING THE ATTIC SPACE WILL BE COMPLETELY CONTAINED | | | WITHIN THE BUILDING THERMAL ENVELOPE. THE ATTIC VENTS | | | ARE REQUIRED TO BE SEALED TO CREATE AN UN-VENTED ATTIC | | | ASSEMBLY. SEE FBC-R 806.4 THE ARCHITECT NEEDS TO | | | CLARIFY THIS IN THE LETTER. | | | | | | 3) AS THIS IS A NEW ADDITION, INDICATE HOW THIS | | | UN-VENTED ATTIC ASSEMBLY WILL BE THERMALLY SEPARATED | | | FROM THE EXISTING VENTED ATTIC SPACE AND HOW THE | | | UN-VENTED ATTIC SPACE IN THE ADDITION WILL BE ACCESSED. | | | FBC 107.2.1 AND FBC-R807.1 | | | | | | |
|