2015-08-01 13:11:43****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SEALCOATING IS REMOVED FROM SCOPE.
  
 STRIPING AND NUMBER OF SPACES TO BE IN ACCORDANCE WITH
 FBC 5TH EDITION ACCESSIBLITY. NO INFORMATION PROVIDED
 REGARDING THE TOTAL NUMBER OF SPACES AND TOTAL NUMBER
 OF ACCESSIBLE SPACES.
  
 AT INSPECTION, PROVIDE THE TOTAL NUMBER OF PARKING
 SPACES AND TOTAL NUMER OF ACCESSIBLE SPACES. THIS IS TO
 BE IN COMPLIANCE WITH FBC 5TH EDITION ACCESSIBLITY
 202.3 (ALTERATIONS), 208.2 (PARKING SPACES), 502
 (PARKING SPACES), 206 (ACCESSIBLE ROUTE). SEE TABLE
 BELOW.
  
 PLAN STATES "STRIPING AS EXISTING CONFIGURATION." IF
 EXISTING IS NOT COMPLIANT WITH THE REQUIREMENTS FOR NEW
 CONSTRUCTION, A COMPLIANT INSTALLATION IS INSTALLED
 (CANNOT BE INSTALLED / STRIPED IN A NON COMPLIANT
 MANNER).
  
 YOU MAY FIND THE FOLLOWING DOCUMENT USEFUL,
 PARTICULARLY THE INTRODUCTION: "WHEN A BUSINESS
 RESTRIPES A PARKING LOT, IT MUST PROVIDE ACCESSIBLE
 PARKING SPACES AS REQUIRED BY THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN."
  
 HTTP://WWW.ADA.GOV/RESTRIPE.HTM
  