| 2015-08-12 14:40:28 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | 1. YOU SHALL SUBMIT A SITE DRAWING TO INDICATE THE | | | LOCATION OF THE PROPOSED OUTSIDE KITCHEN. | | | 2. YOU SHALL PROVIDE A COMPLETE CIRCUIT DIRECTORY OF | | | THE LOAD CENTER FROM WHERE THE POWER IS TO BE SERVED. | | | 3. YOU SHALL PROVIDE SITE SPECIFIC LOAD CALCS AS | | | INDICATED IN NEC 220.83 | | | 4. YOU SHALL INCLUDE ON YOUR DRAWING THE INDIVIDUAL | | | CIRCUIT NUMBERS FOR EACH LOAD. | | | 5. YOU SHALL PROVIDE LIGHTING. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | |
|