| 2015-08-05 09:16:22 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. SUBSTRATE FOR HORIZONTAL INSTALLATIONS HAVE BEEN | | | CHANGED TO CONCRETE BLOCK SUBSTRATE. THE ANCHOR WAS | | | "PANELMATE" ON FIRST SUBMITTAL, BUT HAS BEEN CHANGED TO | | | "ANCHOR & SCREW." PROPOSED ANCHOR SPACING REMAINED THE | | | SAME. | | | | | | A. PLEASE REVISE ANCHOR TO BE CONSISTENT WITH THE | | | PRODUCT APPROVAL. FOR INSTANCE, PAGE 5, SPACING FOR | | | "ALL POINTS SOLID-SET" WAS CIRCLED. IF THIS IS THE | | | ANCHOR PROPOSED, "1/4" SOLID SET" WOULD BE THE ANCHOR. | | | "ANCHOR & SCREW" IS NOT LISTED AS ONE OF THE OPTIONS | | | WITHIN THE PRODUCT APPROVAL. | | | | | | B. SUBSTRATE WAS CHANGED, AND ANCHOR SPACING FOR | | | CONCRETE BLOCK, SPAN < 6 FT WAS CIRCLED. SEE ALL | | | OPENINGS WITH A SPAN GREATER THAN 6' (EXAMPLE 1, 2, 3, | | | ETC); THESE OPENINGS EXCEED 6' SO THE COLUMN FOR SPAN < | | | 8.67 FT SHOULD BE USED. ANCHOR SPACING PROPOSED DOES | | | NOT COMPLY WITH THE REQUIREMENTS OF THE PRODUCT | | | APPROVAL. | | | | | | FBC 5TH EDITION RESIDENTIAL 301.1, WIND LOADS | | | |
|