| 2015-07-30 16:50:07 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 5TH EDITION 2014 |
| | |
| | 1. THE PRODUCT PROPOSED IS NOT CLEAR. A FLAME SPREAD |
| | TEST FOR "BADGER CORK" WAS PROVIDED, SOUND TESTS FOR |
| | QEP PREMIUM 6MM CORK WAS PROVIDED. WHICH PRODUCT IS |
| | BEING INSTALLED? WHAT IS THE RELATIONSHIP BETWEEN |
| | BADGER CORK AND QEP? IF THIS IS THE SAME PRODUCT, |
| | PROVIDE A LETTER FROM THE MANUFACTURER EXPLAINING THE |
| | RELATIONSHIP AND THAT THE PRODUCT TESTED, BADGER CORK, |
| | HAS NOT BEEN MODIFIED AND IS THE EXACT SAME PRODUCT AS |
| | QEP PREMIUM CORK. |
| | |
| | 2. THE TESTS PROVIDED ARE FOR QUARRY TILE, WOOD |
| | FLOORING PROPOSED. PROVIDE THE FOLLOWING TESTS FOR THE |
| | FLOORING PROPOSED: |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST, |
| | PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED |
| | THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE |
| | GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL |
| | NOT BE ALTERED. |
| | |
| | PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART |
| | OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN |
| | DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW |
| | IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT |
| | BELOW WILL NOT BE ALTERED. |
| | |
| | PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. SEE COMMENT REGARDING BADGER CORK. IF THIS IS NOT |
| | THE PRODUCT PROPOSED, SEE FBC 603.1, ALLOWABLE |
| | MATERIALS IN NON COMBUSTIBLE BUILDINGS, SEE ITEM 2, |
| | EXCEPTION 2, ACOUSTICAL INSULATION INSTALLED BETWEEN A |
| | FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 200. |
| | |
| | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM |
| | E 84 OR UL 723. |
| | |
| | |