Plan Review Notes
Plan Review Notes For Permit 15071174
Permit Number 15071174
Review Stop M
Sequence Number 2
Notes
Date Text
2015-08-11 09:50:218/11/15
 MECHANICAL PASSED WITH PROVISO FOR REQUIRED
 VENTILATION.
 PRIOR TO 1ST INSPECTION, THE ENGINEER OF RECORD SHALL
 PROVIDE A CALCULATION TO CERTIFY THAT THE AMOUNT OF
 AMMONIA REFRIGERANT IN POUNDS IN THE WET ADDITION DOES
 NOT EXCEED THE ALLOWABLE AMOUNT PER TABLE 1103.1 FBC-14
 MECHANICAL- 0.014 PER 1000CUBIC FT.
  
 1104.2 MACHINERY ROOM.
 EXCEPT AS PROVIDED IN SECTIONS 1104.2.1 AND 1104.2.2,
 ALL COMPONENTS CONTAINING THE REFRIGERANT SHALL BE
 LOCATED EITHER OUTDOORS OR IN A MACHINERY ROOM WHERE
 THE QUANTITY OF REFRIGERANT IN AN INDEPENDENT CIRCUIT
 OF A SYSTEM EXCEEDS THE AMOUNTS SHOWN IN TABLE 1103.1.
 FOR REFRIGERANT BLENDS NOT LISTED IN TABLE 1103.1, THE
 SAME REQUIREMENT SHALL APPLY WHEN THE AMOUNT FOR ANY
 BLEND COMPONENT EXCEEDS THAT INDICATED IN TABLE 1103.1
 FOR THAT COMPONENT. THIS REQUIREMENT SHALL ALSO APPLY
 WHEN THE COMBINED AMOUNT OF THE BLEND COMPONENTS
 EXCEEDS A LIMIT OF 69,100 PARTS PER MILLION (PPM) BY
 VOLUME. MACHINERY ROOMS REQUIRED BY THIS SECTION SHALL
 BE CONSTRUCTED AND MAINTAINED IN ACCORDANCE WITH
 SECTION 1105 FOR GROUP A1 AND B1 REFRIGERANTS AND IN
 ACCORDANCE WITH SECTIONS 1105 AND 1106 FOR GROUP A2,
 B2, A3 AND B3 REFRIGERANTS.
  
 1106.3 AMMONIA ROOM VENTILATION.
 VENTILATION SYSTEMS IN AMMONIA MACHINERY ROOMS SHALL BE
 OPERATED CONTINUOUSLY AT THE EMERGENCY VENTILATION RATE
 DETERMINED IN ACCORDANCE WITH SECTION 1105.6.3.2.
  
 PLEASE NOTE THAT A REVISION TO THIS PERMIT WILL BE
 REQUIRED FOR ANY MODIFICATIONS TO THE THE WET ADDITION
 OR EXISTING MACHINERY ROOM.
  