Plan Review Notes
Plan Review Notes For Permit 15071174
Permit Number 15071174
Review Stop M
Sequence Number 1
Notes
Date Text
2015-08-05 09:28:461ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15071174
 8/4/15
  
 1) VENTILATION FOR THE REFRIGERATION IN THE WET
 BUILDING ADDITION IS REQUIRED IN ACCORDANCE WITH
 SECTIONS 1104 & 1105 FBC-14 MECHANICAL. THE PLANS DO
 NOT INDICATE ANY EXISTING OR PROPOSED VENTILATION
 SYSTEM, HOWEVER THE NOTE ON SHEET R1.1 INDICATES A
 PERMIT HAS BEEN ISSUED FOR THAT PORTION OF THE PROJECT.
 I HAVE NOT BEEN ABLE TO LOCATE ANY DRAWINGS OR
 CALCULATIONS FOR THE SYSTEM UNDER ANY ISSUED PERMIT.
 PLEASE PROVIDE THE PERMIT NUMBER THE DRAWINGS WERE
 SUBMITTED AND APPROVED UNDER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  