| Plan Review Notes For Permit 15071174 |
| Permit Number |
15071174 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-10 14:47:29 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | | | 1. YOU SHALL SUBMIT A SERVICE RISER DIAGRAM SHOWING THE | | | EXISTING SERVICE AND THE ADDITIONAL LOAD. | | | 2. YOU SHALL PROVIDE LOAD CALCS TO DETERMINE THE | | | ACCEPTABILITY OF THE ADDITIONAL LOADS TO THE EXISTING | | | SERVICE. | | | 3. YOU SHALL PROVIDE WIRING SCHEDULE FOR ALL THE NEW | | | LOADS. | | | 4. A CIRCUIT DIRECTORY SHALL BE PROVIDED. | | | 5. THERE SHALL BE INDICATED ON THE PLANS THE REQUIRED | | | SERVICE OUTLET WITHIN 25? OF EACH CONDENSING UNIT. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|