Plan Review Notes
Plan Review Notes For Permit 15071173
Permit Number 15071173
Review Stop B
Sequence Number 2
Notes
Date Text
2015-10-08 13:23:12BUILDING PLAN REVIEW
 REVISION: 15071173
 PERMIT: 14100350
 ADD: 10130 NORTHLAKE BLVD.
 CONT: HAWKINS
 TEL: (305-796-9695
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. OCT. 08/2015
 ACTION: DENIED
  
 1) THE SCOPE OF THE REVISION SEAMS TO BE GROWING. THE
 REVISON WAS FOR A NEW WINDOW TO THE EXTERIOR AT THE
 PHARMACY. THE SUBMITTED PRODUCT APPROVAL WAS PRINTED TO
 THE WRONG SCALE MAYBE A QUARTER OF THE PLANS SHOW PER
 SHEET, IT APPEARS TO BE ENLARGED.
  
 THE SECOND ISSUE IS THE AUTOVEYOR SYSTEM. THE SUBMITTED
 PAPERWORK FOR THIS SYSTEM IS A DEMENTIONED DRAWING FOR
 FABRICATION PURPOSES ONLY. WE HAVE NOT INFORMATION AS
 TO MATEIALS, DESIGN FOR WIND, MECHANICAL SYSTEMS,
 PNUEMATIC NOR THE ELECTRICAL IT WILL TAKE, SIZE OF
 MOTOR.
 COMMENTS FROM PREVOUS REVIEW:I
 THE SUBMITTED PRODUCT APPROVAL FOR THE DRIVE THRU
 WINDOW 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 PLEASE PROVIDE (2) COPIES OF PRODUCT APPROVAL. FL 17337
 HAS BEEN APPROVAL. PLEASE CIRCLE WHICH SUB-SYSTEM WILL
 BE INSTALLED (4) SUB-SYSTEMS. 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(B) WINDOWS.
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) A SEPARATE PERMIT IS REQUIRED FOR THE UNDERGROUND E.
 F. BAVIS AUTOVEYOR HD.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2015-10-07 16:10:55SENT TO BUILDING/CC