| Plan Review Notes For Permit 15071167 |
| Permit Number |
15071167 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-30 11:09:26 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO COPIES OF A DIAGRAM THAT SHOWS THE | | | DIMENSIONS OF THE SLOPED AND FLAT ROOF AREAS THAT ARE | | | TO BE RE-ROOFED. FBC 107.2.1 | | | | | | 2) SPECIFY THE ROOF SLOPE AND THE MEAN ROOF HEIGHT. FBC | | | 107.2.1 | | | | | | 3) THE ROOF SYSTEM THAT WAS SELECTED FOR THE FLAT ROOF | | | ON PAGE 8 OF NOA NO. 12-0703.06 HAS A MAXIMUM DESIGN | | | PRESSURE OF -60 PSF. THIS IS NOT ADEQUATE FOR ALL OF | | | THE ROOF ZONES AND REQUIRES ENHANCED FASTENING AS | | | ALLOWED BY LIMITATION #7 ON PAGE 10 OF THE NOA. SUBMIT | | | TWO SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | ENHANCED FASTENING IN ACCORDANCE WITH LIMITATION #7. | | | FBC 107.2.1.3 |
|