2015-08-11 20:06:281. SHOW WINDOW OUTLETS AS REQUIRED BY NEC 210.62 ARE
 MISSING
 2. SIGN OUTLETS AS REQUIRED BY NEC 600.5 ARE MISSING.
 3. EMERGENCY LIGHTING SHALL BE INSTALLED IN THE
 COMMUNITY MANAGEMENT & FILE ROOMS.
 4. ADDITIONAL MANDATORY LIGHTING CONTROLS (O/S) ARE
 REQUIRED PER FBC-E 505
  