Plan Review Notes
Plan Review Notes For Permit 15071158
Permit Number 15071158
Review Stop B
Sequence Number 1
Notes
Date Text
2015-07-30 17:26:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 5TH EDITION 2014
  
 TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED
  
 1. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 THE PRODUCT PROPOSED IS ACOUSTICORK, THE FLAME SPREAD
 TEST IS FOR BADGER CORK.
  
 IF THIS IS THE SAME PRODUCT, PROVIDE A LETTER ON
 LETTERHEAD FROM THE MANUFACTURER STATING THE
 RELATIONSHIP BETWEEN ACOUSTICORK AND BADGER CORK AND
 ADDRESS THE ISSUE OF WHETHER THE PRODUCT ITSELF (RESIN
 OR OTHER BONDING AGENTS) HAS CHANGED FROM THE PRODUCT
 THAT WAS TESTED FOR FLAME SPREAD.
  
  
  