| Plan Review Notes For Permit 15071158 |
| Permit Number |
15071158 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-30 17:26:59 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | FBC FLORIDA BUILDING CODE 5TH EDITION 2014 | | | | | | TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED | | | | | | 1. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM | | | E 84 OR UL 723. | | | | | | THE PRODUCT PROPOSED IS ACOUSTICORK, THE FLAME SPREAD | | | TEST IS FOR BADGER CORK. | | | | | | IF THIS IS THE SAME PRODUCT, PROVIDE A LETTER ON | | | LETTERHEAD FROM THE MANUFACTURER STATING THE | | | RELATIONSHIP BETWEEN ACOUSTICORK AND BADGER CORK AND | | | ADDRESS THE ISSUE OF WHETHER THE PRODUCT ITSELF (RESIN | | | OR OTHER BONDING AGENTS) HAS CHANGED FROM THE PRODUCT | | | THAT WAS TESTED FOR FLAME SPREAD. | | | | | | | | | |
|