| 2015-09-09 10:35:28 | THE STAMPED DRAWINGS WERE SUBMITTED AS REQUESTED THIS | | | MORNING. PASSED ELECTRICAL REVIEW. SENT TO LARGE READY | | | BIN "P". MA | | 2015-09-08 15:25:36 | THE LOAD CALCS AND THE PANEL HAVE BEEN REVISED TO | | | MATCH. I NOTIFIED NATE OF THIS BUT AM STILL MISSING THE | | | INCLUSION OF THE SERVICE OUTLET REQUIRED BY NEC 210.63. | | | ONCE I RECEIVE THOSE CORRECTED SHEETS I CAN APPROVED | | | THE PERMIT. |
|