2015-09-03 14:41:58PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 YOUR FAILURE TO PROVIDE THE REQUIRED LOAD CALCS,
 PROMPTED ME TO SEEK THE INFORMATION ON MY OWN. IN GOING
 OVER YOUR SUBMITTAL AND THE NUMBERS THEREIN I NOTICED
 THE FOLLOWING:
  
 1. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD),
 INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR RTU
 AHU-1 OTHERWISE KNOWN ON THE PANEL SCHEDULE AS OA-1
 INDICATES 70AMP. PANEL GL2 CIRCUITS 38/40/42 SHOW TO
 HAVE A 90 AMP DEVICE.
 THE KVA/KW INDICATED ON THE FORM IS 27 YET THE LOAD ON
 THE PANEL PER THE SCHEDULE IS ONLY 11.92. CORRECT THE
 PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO MATCH AND
 ADJUST YOUR CONDUCTORS ACCORDINGLY.
 2. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD),
 INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR RTU
 AHU-2 OTHERWISE KNOWN ON THE PANEL SCHEDULE AS OA-2
 INDICATES 70AMP. PANEL LP2A CIRCUITS 20/22/24 SHOW TO
 HAVE A 90 AMP DEVICE.
 THE KVA/KW INDICATED ON THE FORM IS 27 YET THE LOAD ON
 THE PANEL PER THE SCHEDULE IS ONLY 11.92. CORRECT THE
 PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO MATCH AND
 ADJUST YOUR CONDUCTORS ACCORDINGLY.
 3. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD),
 INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR RTU
 AHU-3 OTHERWISE KNOWN ON THE PANEL SCHEDULE AS OA-3
 INDICATES 70AMP. PANEL SP CIRCUITS 1/3/5 SHOW TO HAVE A
 70 AMP DEVICE. (OK)
 THE KVA/KW INDICATED ON THE FORM IS 27 YET THE LOAD ON
 THE PANEL PER THE SCHEDULE IS ONLY 11.92. CORRECT THE
 PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO MATCH AND
 ADJUST YOUR CONDUCTORS ACCORDINGLY.
 4. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD),
 INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR RTU
 AHU-4 OTHERWISE KNOWN ON THE PANEL SCHEDULE AS OA-4
 INDICATES 70AMP. PANEL SP CIRCUITS 2/4/6 SHOW TO HAVE A
 70 AMP DEVICE. (OK)
 THE KVA/KW INDICATED ON THE FORM IS 27 YET THE LOAD ON
 THE PANEL PER THE SCHEDULE IS ONLY 11.92. CORRECT THE
 PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO MATCH AND
 ADJUST YOUR CONDUCTORS ACCORDINGLY.
 5. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD),
 INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW
 AHU-1, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-1
 INDICATES 30AMP. PANEL GDA CIRCUITS 7/9/11 SHOW TO HAVE
 A 40 AMP DEVICE.
 THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM
 THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT
 IT IS NOT THE 6.3 INDICATED ON THE PANEL SCHEDULE.
 CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO
 MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY.
 6. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD),
 INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW
 AHU-2, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-2
 INDICATES 40AMP. PANEL GDA CIRCUITS 13/15/17 SHOW TO
 HAVE A 50 AMP DEVICE.
 THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM
 THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT
 IT IS NOT THE 8.3 INDICATED ON THE PANEL SCHEDULE.
 CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO
 MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY.
 7. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD),
 INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW
 AHU-3, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-3
 INDICATES 30AMP. PANEL GDA CIRCUITS 14/16/18 SHOW TO
 HAVE A 25 AMP DEVICE.
 THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM
 THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT
 IT IS NOT THE 6.3 INDICATED ON THE PANEL SCHEDULE.
 CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO
 MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY.
 8. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD),
 INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW
 AHU-4, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-4
 INDICATES 20AMP. PANEL GDA CIRCUITS 7/9/11 SHOW TO HAVE
 A 25 AMP DEVICE.
 THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM
 THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT
 IT IS NOT THE 3.72 INDICATED ON THE PANEL SCHEDULE.
 CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO
 MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY.
 9. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD),
 INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW
 AHU-5, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-5
 INDICATES 40AMP. PANEL CDP CIRCUITS 8/10/12 SHOW TO
 HAVE A 50 AMP DEVICE.
 THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM
 THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT
 IT IS NOT THE 7.17INDICATED ON THE PANEL SCHEDULE.
 CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO
 MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY.
 10. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD),
 INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW
 AHU-6, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-6
 INDICATES 40AMP. PANEL GDA CIRCUITS 19/21/23 SHOW TO
 HAVE A 50 AMP DEVICE.
 THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM
 THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT
 IT IS NOT THE 8.4 INDICATED ON THE PANEL SCHEDULE.
 CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO
 MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY.
 11. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD),
 INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW
 AHU-7, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-7
 INDICATES 30AMP. PANEL CDP CIRCUITS 1/3/5 SHOW TO HAVE
 A 40 AMP DEVICE.
 THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM
 THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT
 IT IS NOT THE 5.57 INDICATED ON THE PANEL SCHEDULE.
 CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO
 MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY.
 12. THE MAXIMUM OVERCURRENT PROTECTION DEVICE (OCPD),
 INDICATED ON YOU A/C CHANGE-OUT COMPLIANCE FORM FOR CW
 AHU-8, OTHERWISE KNOWN ON THE PANEL SCHEDULE AS AHU-8
 INDICATES 20AMP. PANEL CDP CIRCUITS 2/4/6 SHOW TO HAVE
 A 40 AMP DEVICE.
 THOUGH THERE IS NO KVA LOAD INDICATED ON THE FORM, FROM
 THE FLC (FULL LOAD CURRENT) IT IS EASILY VISIBLE THAT
 IT IS NOT THE 3.72 INDICATED ON THE PANEL SCHEDULE.
 CORRECT THE PANEL SCHEDULE AND RESPECTIVE LOAD CALCS TO
 MATCH AND ADJUST YOUR CONDUCTORS ACCORDINGLY.
 EVERYTHING INDICATED ABOVE HAS A BEARING ON THE ACTUAL
 LOADS AND CONDUCTOR APPLICATION. REVISE THE PLANS AND
 THE LOAD CALCULATIONS TO MATCH. CORRECT THE CONDUCTORS
 ACCORDINGLY AND RESUBMIT.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  