| Plan Review Notes For Permit 15071078 |
| Permit Number |
15071078 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-08-24 19:18:30 | IT APPEARS THAT THE EC DID NOT UNDERSTAND WHAT WAS | | | REQUIRED OF HIM FOR A PROPER SUBMITTAL. I CALLED HIM | | | AND EXPLAINED IN SPANISH WHAT WAS REQUIRED. I TOLD HIM | | | THAT THE NEMA 14-50 RECEPTACLE REQUIRES A GROUNDED | | | CONDUCTOR (NEUTRAL). HE ARGUED THAT THE EQUIPMENT DID | | | NOT REQUIRE A NEUTRAL. REGARDLESS THE PROPOSED DEVICE | | | REQUIRES A NEUTRAL THEN IF NO NEUTRAL IS REQUIRED | | | CHANGE THE RECEPTACLE TYPE. I ALSO TOLD HIM IN SPANISH | | | THAT I WAS ASKING FOR SPECS ON THE DEVICE BEING | | | INSTALLED. |
|