| 2015-08-03 18:35:43 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | 1. YOU SHALL SUBMIT TWO SET OF DRAWINGS | | | 2. YOU SHALL DECRIBED YOUR SCOPE OF WORK ON THE | | | DRAWINGS | | | 3. PROVIDE LOAD CALCS TO ASCERTAIN CAPACITY FOR THESE | | | DEVICES. | | | 4. YOU SHALL INDICATE HOW THESE DEVICES ARE BEING | | | WIRED. | | | 5. SHOW/INDICATE WHERE THE SOURCE OF POWER AND | | | DISCONNECT FOR THESE OUTLET WILL BE. | | | 6. A SIMPLE WIRING SKETCH OF THE PROPOSED INSTALLATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | |
|