| Date |
Text |
| 2015-07-30 09:22:46 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | |
| | 1) PLEASE REFER TO SECTION R101.4.5 FBC-14 ENERGY |
| | CONSERVATION, CHANGE IN SPACE CONDITIONING: |
| | ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME |
| | CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO |
| | FULL COMPLIANCE WITH THIS CODE. |
| | REFER TO SECTION R101.5.1 COMPLIANCE MATERIALS. |
| | THE FLORIDA BUILDING COMMISSION SHALL APPROVE SPECIFIC |
| | COMPUTER SOFTWARE, WORKSHEETS, COMPLIANCE MANUALS AND |
| | OTHER SIMILAR MATERIALS THAT MEET THE INTENT OF THIS |
| | CODE. COMMISSION APPROVED CODE COMPLIANCE DEMONSTRATION |
| | FORMS CAN BE FOUND IN TABLE R101.5.1. |
| | |
| | TABLE R101.5.1 INDEX TO CODE COMPLIANCE |
| | |
| | FORM R402 |
| | FLORIDA RESCHECK COMPUTER PRINTOUT |
| | FORM R405 (COMMISSION APPROVED SOFTWARE PRINTOUT) |
| | APPENDIX C |
| | |
| | R101.5.1.1 RESIDENTIAL BUILDINGS THREE STORIES OR LESS. |
| | R101.5.1.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| | SHALL BE SUBMITTED TO THE CODE OFFICIAL TO DEMONSTRATE |
| | CODE COMPLIANCE BY THIS METHOD. ALTERNATIVELY, A |
| | FLORIDA RESCHECK COMPUTER PRINTOUT MAY BE SUBMITTED TO |
| | DEMONSTRATE COMPLIANCE BY SECTIONS R402, R403 AND R404. |
| | R101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) |
| | DEMONSTRATING THAT CODE COMPLIANCE HAS BEEN ACHIEVED |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL FOR |
| | COMPLIANCE BY SECTION R405. |
| | |
| | PLEASE CHOOSE EITHER THE PRESCRIPTIVE OR PERFORMANCE |
| | BASED COMPLIANCE PATH AS INDICATED ABOVE, AND SUBMIT |
| | THE COMPLIANCE FORMS IN DUPLICATE. PLEASE NOTE |
| | MODIFICATIONS TO THE GARAGE STRUCTURE, THERMAL |
| | ENVELOPE, AND MEP SYSTEMS MAY BE REQUIRED TO MEET |
| | COMPLIANCE, THEREFORE REVISED PLANS MUST BE SUBMITTED. |
| | |
| | 2) THE SUBMITTED RHEEM DESIGN STAR AC LOAD CALCULATION |
| | PROGRAM IS INTENDED FOR USE WITH RHEEM PRODUCTS ONLY. |
| | PLEASE SUBMIT A SIZING CALCULATION IN ACCORDANCE WITH |
| | ACCA MANUAL J- REFER TO SECTION R403.6.1 FBC-14 ENERGY |
| | CONSERVATION. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |