| Plan Review Notes For Permit 15071074 |
| Permit Number |
15071074 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-30 12:18:50 | HAD THIS APPLICATION BEEN APPROVED BY MECHANICAL THE | | | FOLLOWING COMMENTS COULD HAVE BEEN ADDRESS VIA | | | PROVISOS, BUT SINCE THERE ARE MAJOR CORRECTIONS | | | REQUIRED FOR THE MECHANICAL REVIEW. I DIDN'T THINK TO | | | BE DAMAGING TO GET THE CORRECTIONS ADDRESSED ON THE | | | SUBMITTAL. | | | | | | 1. PER FBC STANDARDS THE ADDITION OF THIS UNIT TO THE | | | GARAGE CONVERTS THE SPACE INTO CONDITIONED HABITABLE | | | SPACE, WHICH MAY REQUIRE ADDITIONAL ITEMS SUCH AS HEAT | | | AND PROPER OUTLET PLACEMENT. | | | 2. PER NEC 2011 SECTION 300.9, CONDUCTORS INSIDE OF ANY | | | EXPOSED EXTERIOR RACEWAY SHALL BE LISTED FOR WET | | | LOCATION. | | | 3. PER NEC 210.63, A SERVICE OUTLET IS REQUIRED WITHIN | | | 25' OF CONDENSING UNIT. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | | | 2015-07-30 10:15:34 | ROUTED TO ELECTRICAL/CC |
|