2015-07-30 12:18:50HAD THIS APPLICATION BEEN APPROVED BY MECHANICAL THE
 FOLLOWING COMMENTS COULD HAVE BEEN ADDRESS VIA
 PROVISOS, BUT SINCE THERE ARE MAJOR CORRECTIONS
 REQUIRED FOR THE MECHANICAL REVIEW. I DIDN'T THINK TO
 BE DAMAGING TO GET THE CORRECTIONS ADDRESSED ON THE
 SUBMITTAL.
  
 1. PER FBC STANDARDS THE ADDITION OF THIS UNIT TO THE
 GARAGE CONVERTS THE SPACE INTO CONDITIONED HABITABLE
 SPACE, WHICH MAY REQUIRE ADDITIONAL ITEMS SUCH AS HEAT
 AND PROPER OUTLET PLACEMENT.
 2. PER NEC 2011 SECTION 300.9, CONDUCTORS INSIDE OF ANY
 EXPOSED EXTERIOR RACEWAY SHALL BE LISTED FOR WET
 LOCATION.
 3. PER NEC 210.63, A SERVICE OUTLET IS REQUIRED WITHIN
 25' OF CONDENSING UNIT.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  