| 2015-09-22 15:18:04 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | |
| | 2- SPECIFY ATTIC ACCESS AS REQUIRED BY SEC. R807 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 3- ENERGY CALCULATIONS SUBMITTED: |
| | A) NEED TO PROVIDE CURRENT FORM FOR 2014 CODE. SEC. |
| | R101.5.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). THERE ARE TWO OPTIONS: PRESCRIPTIVE (FORM 402) |
| | OR SIMULATED (FORM 405). |
| | |
| | B) PROVIDE A LEGIBLE COPY. SEC. 107.2.1.4 CITY |
| | AMENDMENTS. |
| | |
| | C) REVISE NAME OF THE BUILDER. SEC. R101.5.1.1.1 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | D) REVISE ITEM # 6. SEE GENERAL INSTRUCTION #2 ON FIRST |
| | PAGE AND NOTE # (1) ON SECOND PAGE. ALL THE VALUES TO |
| | BE INSTALLED NEED TO MEET OR EXCEED THE PERFORMANCE |
| | CRITERIA ON PAGE TWO. |
| | |
| | E) REVISE ITEM #9. SEE GENERAL INSTRUCTION NOTE #2 ON |
| | FIRST PAGE AND NOTE #3 ON SECOND PAGE. |
| | |
| | F) OWNER/AGENT TO CERTIFY BOTTOM OF FORM AS REQUIRED BY |
| | SEC. R103.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | NOTE: BUILDER WILL NEED TO PROVIDE COMPLIANCE WITH THE |
| | WINDOWS AND DOORS U-DACTOR AND SHGC FACTOR SPECIFIED ON |
| | THE ENERGY CALCULATIONS. |
| | |
| | 4- ENGINEER OF RECORD TO PROVIDE DETAIL SHOWING |
| | COMPLIANCE WITH THE MASONRY INSULATION AS SHOWN ON THE |
| | ENERGY CALCULATIONS. NEED INSULATION FOR THE INTERIOR |
| | OF WALL AND EXTERIOR OF WALL. SEE NOTE: #3 ON SECOND |
| | PAGE OF ENERGY CALCULATIONS SUBMITTED. SEC. R103.2 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | 5- TRUSS PACKAGE SUBMITTED; |
| | A) TRUSS DESIGN ENGINEER TO PROVIDE ORIGINAL SIGNATURE |
| | (NO RUBBER STAMP) ON ALL DRAWINGS AS REQUIRED BY |
| | CHAPTER 471 F.S. |
| | |
| | B) COVER SHEET DOESN'T COMPLY WITH SEC. 61G15-31.003: |
| | (1) MISSING THE INFORMATION FORM THE STRUCTURAL |
| | ENGINEER OF RECORD. (2) THE ADDRESS OF THE PROJECT IS |
| | INCORRECT. (3) THE CURRENT CODE IS THE 2014 NOT 2010. |
| | (4) "EACH OF THE DRAWINGS IN THE TRUSS DESIGN PACKAGE |
| | FOR INDIVIDUAL TRUSSES SHALL INCLUDE A TITLE BLOCK |
| | BEARING THE PRINTED NAME, ADDRESS AND LICENSE NUMBER OF |
| | THE TRUSS DESIGN ENGINEER AND THE DATE OF THE DRAWING". |
| | |
| | C) TRUSS PACKAGE NEEDS TO BE REVIEWED AND APPROVED BY |
| | THE ENGINEER OF RECORD PRIOR TO SUBMITTAL. |
| | |
| | 6- TRUSS PACKAGE SUBMITTED DOESN'T INCLUDE REPAIRS FOR |
| | EXISTING WOOD TRUSSES AS SPECIFIED ON THE STRUCTURAL |
| | DRAWINGS. PROVIDE TRUSS PACKAGE FOR REPAIRED/ALTERED |
| | TRUSSES. SEC. R301. |
| | |
| | 7- ADDRESS SHOWN ON THE REPORT OF GEOTECHNICAL STUDY IS |
| | INCORRECT. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 8- SIZE OF FOOTING SHOWN ON SHEET S1 DOESN'T MATCH |
| | RECOMMENDATIONS SHOWN ON THE REPORT OF GEOTECHNICAL |
| | STUDY SUBMITTED. ENGINEER OF RECORD TO REVIEW THE |
| | REPORT OF GEOTECHNICAL STUDY AND REVISE FOOTING SIZE |
| | ACCORDINGLY OR PROVIDE WRITTEN RESPONSE STATING WHY NOT |
| | CHANGING THE FOOTING SIZE PER THE REPORT |
| | RECOMMENDATIONS. SEC. 107.2.1.3 CITY AMENDMENTS. |
| | |
| | 9- ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| | REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF USING |
| | SCREWS, THEN SPECIFY SIZE AND NUMBER OF SCREWS AND |
| | SPECIFY THE TILE UPLIFT MOMENT. IF SPECIFYING TILE |
| | ADHESIVE, THEN PROVIDE THE PRODUCT APPROVAL LISTED ON |
| | THE TILE PRODUCT APPROVAL. |
| | |
| | 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) HORIZONTAL SLIDER WINDOW SIZE SPECIFIED ON THE |
| | PLANS. NOA 14-0915.07 SUBMITTED DOESN'T COVER SIZE |
| | SPECIFIED ON PLANS (76" X 66"). |
| | |
| | B) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF |
| | RECORD. SEE TILE PRODUCT APPROVAL FOR LISTED ADHESIVES. |
| | |
| | C) ROOF TILE UNDERLAYMENT. PROVIDE LEGIBLE PRODUCT |
| | APPROVAL. LETTERING ON THE FLORIDA PRODUCT APPROVAL |
| | FL11288-R13 SUBMITTED IS TOO SMALL. COPYING TWO PAGES |
| | INTO ONE MAKES THE LETTERING TOO SMALL. ALSO, CLEARLY |
| | IDENTIFY SPECIFIC UNDERLAYMENT TO BE USED TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES. |
| | |
| | D) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | 11- PRODUCT APPROVAL NUMBERS SHOWN ON PLANS DON'T MATCH |
| | PRODUCT APPROVALS SUBMITTED. REVISE AS REQUIRED TO |
| | MATCH TO AVOID CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 12- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| | SUBMIT OLD COPIES FOR REFERENCE. |
| | |