Plan Review Notes
Plan Review Notes For Permit 15071062
Permit Number 15071062
Review Stop B
Sequence Number 1
Notes
Date Text
2015-09-22 15:18:04RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC-5TH EDITION (2014).
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- SPECIFY ATTIC ACCESS AS REQUIRED BY SEC. R807 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- ENERGY CALCULATIONS SUBMITTED:
 A) NEED TO PROVIDE CURRENT FORM FOR 2014 CODE. SEC.
 R101.5.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). THERE ARE TWO OPTIONS: PRESCRIPTIVE (FORM 402)
 OR SIMULATED (FORM 405).
  
 B) PROVIDE A LEGIBLE COPY. SEC. 107.2.1.4 CITY
 AMENDMENTS.
  
 C) REVISE NAME OF THE BUILDER. SEC. R101.5.1.1.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) REVISE ITEM # 6. SEE GENERAL INSTRUCTION #2 ON FIRST
 PAGE AND NOTE # (1) ON SECOND PAGE. ALL THE VALUES TO
 BE INSTALLED NEED TO MEET OR EXCEED THE PERFORMANCE
 CRITERIA ON PAGE TWO.
  
 E) REVISE ITEM #9. SEE GENERAL INSTRUCTION NOTE #2 ON
 FIRST PAGE AND NOTE #3 ON SECOND PAGE.
  
 F) OWNER/AGENT TO CERTIFY BOTTOM OF FORM AS REQUIRED BY
 SEC. R103.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE: BUILDER WILL NEED TO PROVIDE COMPLIANCE WITH THE
 WINDOWS AND DOORS U-DACTOR AND SHGC FACTOR SPECIFIED ON
 THE ENERGY CALCULATIONS.
  
 4- ENGINEER OF RECORD TO PROVIDE DETAIL SHOWING
 COMPLIANCE WITH THE MASONRY INSULATION AS SHOWN ON THE
 ENERGY CALCULATIONS. NEED INSULATION FOR THE INTERIOR
 OF WALL AND EXTERIOR OF WALL. SEE NOTE: #3 ON SECOND
 PAGE OF ENERGY CALCULATIONS SUBMITTED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 5- TRUSS PACKAGE SUBMITTED;
 A) TRUSS DESIGN ENGINEER TO PROVIDE ORIGINAL SIGNATURE
 (NO RUBBER STAMP) ON ALL DRAWINGS AS REQUIRED BY
 CHAPTER 471 F.S.
  
 B) COVER SHEET DOESN'T COMPLY WITH SEC. 61G15-31.003:
 (1) MISSING THE INFORMATION FORM THE STRUCTURAL
 ENGINEER OF RECORD. (2) THE ADDRESS OF THE PROJECT IS
 INCORRECT. (3) THE CURRENT CODE IS THE 2014 NOT 2010.
 (4) "EACH OF THE DRAWINGS IN THE TRUSS DESIGN PACKAGE
 FOR INDIVIDUAL TRUSSES SHALL INCLUDE A TITLE BLOCK
 BEARING THE PRINTED NAME, ADDRESS AND LICENSE NUMBER OF
 THE TRUSS DESIGN ENGINEER AND THE DATE OF THE DRAWING".
  
 C) TRUSS PACKAGE NEEDS TO BE REVIEWED AND APPROVED BY
 THE ENGINEER OF RECORD PRIOR TO SUBMITTAL.
  
 6- TRUSS PACKAGE SUBMITTED DOESN'T INCLUDE REPAIRS FOR
 EXISTING WOOD TRUSSES AS SPECIFIED ON THE STRUCTURAL
 DRAWINGS. PROVIDE TRUSS PACKAGE FOR REPAIRED/ALTERED
 TRUSSES. SEC. R301.
  
 7- ADDRESS SHOWN ON THE REPORT OF GEOTECHNICAL STUDY IS
 INCORRECT. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 8- SIZE OF FOOTING SHOWN ON SHEET S1 DOESN'T MATCH
 RECOMMENDATIONS SHOWN ON THE REPORT OF GEOTECHNICAL
 STUDY SUBMITTED. ENGINEER OF RECORD TO REVIEW THE
 REPORT OF GEOTECHNICAL STUDY AND REVISE FOOTING SIZE
 ACCORDINGLY OR PROVIDE WRITTEN RESPONSE STATING WHY NOT
 CHANGING THE FOOTING SIZE PER THE REPORT
 RECOMMENDATIONS. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 9- ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF USING
 SCREWS, THEN SPECIFY SIZE AND NUMBER OF SCREWS AND
 SPECIFY THE TILE UPLIFT MOMENT. IF SPECIFYING TILE
 ADHESIVE, THEN PROVIDE THE PRODUCT APPROVAL LISTED ON
 THE TILE PRODUCT APPROVAL.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) HORIZONTAL SLIDER WINDOW SIZE SPECIFIED ON THE
 PLANS. NOA 14-0915.07 SUBMITTED DOESN'T COVER SIZE
 SPECIFIED ON PLANS (76" X 66").
  
 B) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF
 RECORD. SEE TILE PRODUCT APPROVAL FOR LISTED ADHESIVES.
  
 C) ROOF TILE UNDERLAYMENT. PROVIDE LEGIBLE PRODUCT
 APPROVAL. LETTERING ON THE FLORIDA PRODUCT APPROVAL
 FL11288-R13 SUBMITTED IS TOO SMALL. COPYING TWO PAGES
 INTO ONE MAKES THE LETTERING TOO SMALL. ALSO, CLEARLY
 IDENTIFY SPECIFIC UNDERLAYMENT TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES.
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 11- PRODUCT APPROVAL NUMBERS SHOWN ON PLANS DON'T MATCH
 PRODUCT APPROVALS SUBMITTED. REVISE AS REQUIRED TO
 MATCH TO AVOID CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
  
 12- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT OLD COPIES FOR REFERENCE.
  