| Plan Review Notes For Permit 15071043 |
| Permit Number |
15071043 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-10-04 05:15:57 | 1) IT IS DIFFICULT TRYING TO REVIEW THE PLANS FROM ON | | | SECTION OF AN AREA TO ANOTHER. PLEASE PLACE MATCH LINES | | | ON THE FLOOR PLANS ( ADE & AE) DRAWINGS TO ASSIST IN A | | | TIMELY REVIEW OF THIS PROJECT. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 2) SHT.AE420 -DETAILS #1 &2 - SUBMIT DETAILS HOW THE | | | PIPE SUPPORTS/STANDS ARE ATTACHED TO THE EXISTING ROOF. | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SHT. AE611 - MEN & WOMEN'S ACCESSIBLE TOILET STALL- | | | SHOW THAT THE LAVATORY DOES NOT ENCROACH INTO THE CLEAR | | | FLOOR SPACE FOR THE WATER CLOSET. FBC-ACCESS. | | | SEC.604.3. | | | 4) SHT.AE612 - SHOW THE MOUNTING HEIGHTS OF THE GRAB | | | BARS ABOVE THE FINISH FLOOR. HEIGHTS SHALL BE MEASURED | | | TO THE TOP OF THE GRIPPING SURFACE. FBC-ACCESS. SEC. | | | 609.4. | | | 5) SHT. AE613 - DETAIL #2 - SHOW THE REQUIRED CLEAR | | | FLOOR SPACE (LXW) FOR THE WATER CLOSET AS REQD. BY | | | FBC-ACCESS. SEC.604.3. | | | 6) SHT. AE613 - DETAIL #2 SHOWS THE CENTERLINE OF THE | | | ACCESSIBLE WATER CLOSET 20 INCHES FROM THE SIDE WALL. | | | THE CENTERLINE OF THE WATER CLOSET SHALL BE 16-18 | | | INCHES FROM THE SIDE WALL.FBC-ACCESS. SEC.604.2. | | | 7) SHT. AE614 - DETAIL 1A - SHOW THE HEIGHT OF THE | | | SHOWER SEAT FROM THE FINISH FLOOR. THE HEIGHT SHALL BE | | | 17-19 INCHES ABOVE THE FINISH FLOOR. FBC-ACCESS | | | SEC.610.2. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|