| Plan Review Notes For Permit 15071043 |
| Permit Number |
15071043 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-10-15 14:27:52 | MECHANICAL APPROVED WITH EXCEPTIONS. | | | SUBMITTALS REQUIRED PRIOR TO 1ST INSPECTION: | | | | | | 1) ENERGY CALCULATIONS | | | 2) EXTERIOR PIPE INSULATION AND UV PROTECTION. | | | 3) WIND LOAD TIE DOWN ENGINEERING FOR THE ROOFTOP PIPE | | | SUPPORT STANDS AND CURBS. | | | 4) FIRE DAMPERS | | | 5) FL. PRODUCT APPROVALS/MIAMI-DADE NOA'S FOR THE | | | DRAINABLE O/A LOUVERS. | | | | | | PLEASE NOT ALL FUTURE MECHANICAL LAYOUT PLANS MUST | | | CLEARLY SHOW THE LOCATIONS OF FIRE-RATED WALLS AND | | | FIRE-RATED CEILING ASSEMBLIES. |
|