| Date |
Text |
| 2015-07-30 10:58:48 | 1451 SOUTH OLIVE AVENUE |
| | PERMIT #15071043 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET ADE001: PROVIDE DRAWING NOTE INDICATING ALL |
| | CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE |
| | REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS |
| | SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | SHEET ADE001: PROVIDE DRAWING NOTE INDICATING, "FIRE |
| | PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED BY EMAIL ([email protected]) AND APPROVED BY |
| | THE OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH |
| | DIXIE HIGHWAY." |
| | |
| | LIFE SAFETY PLANS ARE DIFFICULT TO READ DUE TO |
| | EXTREMELY LIGHT AND DARK DRAWING LINE WEIGHTS. PLANS |
| | SHALL INDICATE FIRE RATED WALLS, EXIT TRAVEL DISTANCES, |
| | COMMON PATH OF TRAVEL DISTANCE, DEAD-END CORRIDOR |
| | LENGTHS, ETC. |
| | |
| | SHEET AE121.4 & AE121M.4: THE ADD/ALTERNATE STORAGE |
| | MEZZANINE APPEARS TO CREATE A COMMON PATH OF TRAVEL OF |
| | APPROXIMATELY 130 - 150 FEET TO REACH AN EXIT/EXIT |
| | ACCESS CORRIDOR. FULLY SPRINKLERED STORAGE OCCUPANCIES |
| | ARE LIMITED TO A COMMON PATH OF TRAVEL OF 100 FEET. |
| | |
| | SHEET AE121.4: WOODSHOP C164 REQUIRES A 1-HOUR FIRE |
| | BARRIER HAZARD SEPARATION FROM THE STORAGE OCCUPANCY |
| | PER NFPA 1 SECTION 8.7 - SPECIAL HAZARD PROTECTION. |
| | |
| | SHEET AE121.4: HOW WILL WOODSHOP C164 BE PROTECTED TO |
| | PREVENT A DUST EXPLOSION? PER NFPA 101 SECTION 8.7.2 - |
| | EXPLOSION PROTECTION, WHERE HAZARDOUS PROCESSES OR |
| | STORAGE IS OF SUCH A CHARACTER AS TO INTRODUCE AN |
| | EXPLOSION POTENTIAL, AN EXPLOSION VENTING SYSTEM OR AN |
| | EXPLOSION SUPPRESSION SYSTEM SPECIFICALLY DESIGNED FOR |
| | THE HAZARD INVOLVED SHALL BE PROVIDED. |
| | |
| | SHEET AE121.4: MOTHERS' ROOM #C170 APPEARS TO BE |
| | LOCATED BELOW THE FIRE RATED STAIR AND WILL REQUIRE THE |
| | CEILING AND DOOR TO BE PROVIDED WITH A FIRE RATING |
| | EQUAL TO THE PROTECTED STAIR ENCLOSURE. |
| | |
| | SHEET AE121M.4: EXISTING PLANS INDICATE THERE IS A |
| | LARGE STORAGE ROOM (C205) TO THE WEST OF STAIR #1 THAT |
| | HAS ACCESS TO BOTH STAIR #1 & STAIR #2. THIS FLOOR PLAN |
| | APPEARS TO ELIMINATE ACCESS TO STAIR #2 FROM THE |
| | STORAGE ROOM. |
| | |
| | SHEET AE121M.4: PLANS DO NOT INDICATE OF EITHER |
| | STAIRWELL #1 ENTRANCE DOOR HAS AN EXISTING FIRE RATING. |
| | |
| | SHEET AE121M.4: STAIRWELL #2 DOOR C212 DOES NOT |
| | INDICATE A FIRE RATING AND IS NOT LOCATED IN THE DOOR |
| | SCHEDULE. |
| | |
| | ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE |
| | REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE |
| | BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN |
| | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED |
| | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |