| 2015-11-30 18:15:10 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. FBC 5TH EDITION 301.1, DESIGNER IS TO ELECT |
| | COMPLIANCE METHOD. EXISTING BUILDING IS BEING RENOVATED |
| | (BY AFFECTING THE EXITING AT THE REAR) AND THE PROPOSED |
| | CONSTRUCTION IS AN ADDITION. |
| | |
| | 3RD REVIEW, METHOD OF ALTERATION NOT STATED. |
| | |
| | 2. FBC 5TH EDITION CHAPTER 11, NO INFORMATION PROVIDED |
| | FOR THIS ADDITION TO AN ASSEMBLY OCCUPANCY BUILDING |
| | REGARDING ANY OF THE ITEMS IN THIS CHAPTER. PROVIDE |
| | PLANS TO ADDRESS ALL. BASIC INFORMATION SUCH AS |
| | OCCUPANCY CLASSIFICATION (FBC CHAPTER 3) NOT PROVIDED. |
| | NO OCCUPANCY SEPARATION SHOWN, A 6" STEP IS SHOWN BUT |
| | NO ACCESSIBILITY COMPLIANCE INFORMATION PROVIDED. THE |
| | PLAN APPEARS TO ROUTE TWO ASSEMBLY OCCUPANCY EXITS |
| | THROUGH A NEW STORAGE ROOM (OCCUPANCY CLASSIFICATION |
| | NOT STATED, S1 OR S2?). THERE ARE MANY REFERENCES TO |
| | THE "NEW BUILDING" BUT TO BE CONSIDERED A SEPARATE |
| | BUILDING, A FIRE WALL IS REQUIRED, NONE SHOWN. |
| | |
| | 3RD REVIEW, ADDITIONAL INFORMATION WAS PROVIDED BUT |
| | OCCUPANCY CLASSIFICATION NOT STATED, AND THE |
| | ELIMINATION OF TWO EXITS NOT ADDRESSED, ACCESSIBILITY |
| | NOT PROPERLY ADDRESSED. PROVIDE A LIFE SAFETY PLAN |
| | WHICH SHOWS HOW THE PROPOSED RENOVATION AFFECTS |
| | EXITING. INCLUDE OCCUPANT LOAD, EXIT LIGHTS, TRAVEL |
| | DISTANCE, ALL OTHER APPLICABLE INFORMATION, FBC CHAPTER |
| | 10. A STATEMENT IN THE RESPONSE LETTER THAT |
| | ACCESSIBILITY AND EXITING IS MAINTAINED THROUGH THE |
| | FRONT IS NOT ADEQUATE. |
| | |
| | 3. PROPOSED RENOVATION APPEARS TO ELIMINATE TWO EXITS, |
| | BUT NO LIFE SAFETY PLAN PROVIDED. PROVIDE A LIFE SAFETY |
| | PLAN TO SHOW HOW ELIMINATION OF TWO DOORS WILL AFFECT |
| | THE EXITING FOR THIS BUILDING. |
| | |
| | 3RD REVIEW, NOT ADDRESSED. SEE COMMENT #2. EXITING AND |
| | ACCESSIBLE EXITING NOT CLEAR. |
| | |
| | A SET HAS BEEN RETAINED. |
| | |
| | 4. CALCULATIONS FOR THE ROOF WERE PROVIDED. PROVIDE THE |
| | PRODUCT APPROVAL, FAC9N-3. |
| | |