| Plan Review Notes For Permit 15071032 |
| Permit Number |
15071032 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-02 16:55:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) ONLY ONE SET OF PLAN DRAWINGS WAS PROVIDED, TWO | | | SHALL BE PROVIDED FOR FINAL APPROVAL. | | | | | | 2) THERE APPEARS TO BE TWO DOORS LEADING FROM THE MAIN | | | BLDG THAT MAY BE REQUIRED EXIT DOORS. EXIT DOORS CAN | | | NOT PASS THRU A STORAGE AREA. | | | | | | 3) PROVIDE A LIFE SAFETY PLAN. | | | | | | 4) TWO CEILING FANS ARE BEING PROVIDED. IF THIS IS A | | | STORAGE AREA, WHAT TYPE OF MATERIAL WILL BE STORED | | | HERE. | | | | | | 5) NO EXIT SIGN IS PROVIDED AT THE EXTERIOR DOOR. | | | | | | 6) IS THE MAIN BUILDING SPRINKLERED OR CONTAIN A FIRE | | | ALARM. ANY LIFE SAFETY SYSTEM SHALL BE EXTENDED INTO | | | THE PROPOSED STORAGE AREA. | | | | | | 7) NO EMERGENCY LIGHTING IS INDICATED. |
|