| Date |
Text |
| 2016-01-14 15:38:05 | YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED |
| | DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL |
| | REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED |
| | BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO |
| | SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE |
| | REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION |
| | OF ANY PREVIOUS COMMENTS. |
| | |
| | 1. YOU SHALL PROVIDE A SITE PLAN INDICATING THE |
| | LOCATION OF THE MAIN SERVICE TO THE RESIDENCE. THOUGH |
| | ZONING HAS PERMITTED THE SECOND METER, BOTH FPL & THE |
| | NATIONAL ELECTRICAL CODE RESTRICT THE DROPS TO ONE PER |
| | LOT. IT IS NOT MY INTENT TO DESIGN YOUR SERVICE, BUT I |
| | CAN RECOMMEND THAT YOU MODIFY THE EXISTING SERVICE AND |
| | ADD A TWO GANG METER SOCKET WITH A MAIN FOR THE COTTAGE |
| | AND PROCEED FROM THERE TO THE REAR PANEL. PLEASE MAKE |
| | CERTAIN TO INCLUDE A PROPER GROUND FOR THE DETACHED |
| | STRUCTURE. |
| | 2. A LAUNDRY CIRCUIT WILL NOT BE REQUIRED FOR THE |
| | COTTAGE UNLESS IT IS TO BE A SEPARATE DWELLING. |
| | THEREFORE, IF METERED SEPARATELY, A LAUNDRY CIRCUIT |
| | SHALL BE PROVIDED. |
| | 3. PER FBC-R 303.9, YOU SHALL PROVIDE HEAT CAPABLE OF |
| | MAINTAINING 68 DEGREES F, THREE FT. ABOVE THE FLOOR |
| | ETC. REVISE YOUR HVAC AND LOAD CALCS ACCORDINGLY. |
| | 5. CORRECT YOUR LOAD CALCS TO INCLUDE THE REQUIRED HEAT |
| | AND LAUNDRY CIRCUIT IF APPLICABLE. FIGURE THE LOADS AS |
| | PER NEC 220.83. |
| | |
| | THE REST CAN BE ADDRESSED WITH NOTES ON THE PLANS. |
| | 4. NEC 406.12 REQUIRES THAT ALL 15 & 20 AMP NON?LOCKING |
| | RECEPTACLES IN DWELLING UNITS BE TAMPER?RESISTANT. |
| | 6. NEC 314.27(A)(2), CEILING OUTLET BOXES SHALL BE |
| | LISTED TO SUPPORT A MINIMUM OF 50LBS. |
| | 7. NEC 314.27(C) REQUIRES THAT CEILING BOXES USED TO |
| | SUPPORT CEILING FANS BE LISTED AND MARKED FOR THE |
| | PURPOSE. |
| | 8. NEC 406.12 REQUIRES THAT 15 & 20 AMP RECEPTACLES IN |
| | WET LOCATIONS (OUTDOORS) BE LISTED WEATHER RESISTANT, |
| | "WR". |
| | 9. FBC-R SECTION 314 REQUIRES THAT YOU INSTALL SMOKE |
| | DETECTORS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE?SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |