Plan Review Notes
Plan Review Notes For Permit 15071022
Permit Number 15071022
Review Stop E
Sequence Number 2
Notes
Date Text
2015-12-28 14:52:41YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED
 DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL
 REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED
 BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO
 SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE
 REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION
 OF ANY PREVIOUS COMMENTS.
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE
 EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE) AND THE
 FBC, (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF
 WEST PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL.
 0- YOU FAILED TO PROVIDE A RESPONSE LETTER ADDRESSING
 THE ELECTRICAL DEFICIENCIES.
 1- YOU SHALL PROVIDE THE REQUESTED SITE PLAN MARKED
 WITH THE LOCATION OF THE ELECTRICAL SERVICE DROP, THE
 EXISTING SERVICE EQUIPMENT AND ANY PROPOSED NEW WORK TO
 THE SERVICE AND/OR EQUIPMENT. INCLUDE ALL SERVICE
 DISCONNECTS AS WELL. THIS IS TO ASCERTAIN COMPLIANCE
 WITH NEC 230.2
 2- NOT REQUIRED FOR THE COTTAGE.
 3? 5 SATISFACTORILY ADDRESSED.
 6? 9 YOU FAILED TO ADDRESS THE NOTED DEFICIENCIES.
 CORRECT THE PLANS ACCORDINGLY
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  
  