Plan Review Notes
Plan Review Notes For Permit 15071022
Permit Number 15071022
Review Stop B
Sequence Number 2
Notes
Date Text
2015-12-17 17:29:51RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 NOTE: THE COMMENTS BELOW MAY BE APPROVED WITH PROVISO.
 REVISION FEES MAY APPLY. CONTRACTOR TO ADVICE IF
 PROVISO OPTION IS PREFERRED OR IF RE-SUBMITTING
 REQUIRED INFORMATION BEFORE ISSUING THE PERMIT.
  
  
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 811
 OF FBC-EXISTING BUILDING, 5TH EDITION (2014).
 NOTE: PLEASE COORDINATE ENERGY CALCULATIONS WITH PLANS
 SUBMITTED TO AVOID CONFLICTS OR DELAYS.
 (10/1/15 GOT CONFIRMATION FROM FRIEDERIKE MITTNER. THIS
 IS A CONTRIBUTING HISTORIC BUILDING. THEREFORE ENERGY
 CALCULATIONS ARE NOT REQUIRED.
 CALLED CONTRACTOR PAUL NEWMAN TO NOTIFY HIM ABOUT THE
 ENERGY CALCULATIONS).
  
 RESPONSE: ENERGY CALCULATIONS WERE SUBMITTED ANYWAY.
 ENERGY CALCULATIONS NEED NO TO BE SUBMITTED BECAUSE THE
 HOUSE A A TRUE CONTRIBUTING HISTORIC HOUSE. IF
 CONTRACTOR WANTS TO SUBMITTED THEM, THEN THEY NEED TO
 BE CORRECT. REVISE THE FOLLOWING:
 A) REVISE ITEM #1. THIS IS EXISTING BUILDING NOT NEW
 CONSTRUCTION. SEC. R101.5.1.1.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) REVISE ITEM #10. R-VALUE TO MATCH PLANS. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) REVISE THE ROOF TYPE SHOWN ON PAGE 2 OF 4. SEE PLANS
 AND REVISE AS REQUIRED. THE ROOF TYPE IS NOT HIP. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 D) CLARIFY WHY THE CEILING R-VALUE ON PAGE 2 OF 4 IS
 0.1. SEE ITEM #10 ON COVER PAGE AND ARCHITECTURAL
 PLANS. REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2
 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 E) DOOR ORIENTATION ON PAGE 3 OF 4 IS INCORRECT. SEE
 PLANS/SURVEY AND REVIEW AS REQUIRED. SEC. R101.5.1.1.2
 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 F) WINDOWS ORIENTATION ON PAGE 3 OF 4 IS INCORRECT. SEE
 PLANS AND SURVEY AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 G) COMPLETE THE AIR BARRIER AND INSULATION INSPECTION
 SHEET. SEC R405.4.2 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014)
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON-THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) PROPOSED ROOF SHINGLES AS SPECIFIED ON THE
 ARCHITECT'S PLANS.
  
 RESPONSE: PRODUCT APPROVAL WAS NOT SUBMITTED.
  
 B) EXTERIOR SWING DOOR THAT MATCHES DOOR #2 SPECIFIED
 BY THE ARCHITECT. AND NEED TO PROVIDE PRODUCT APPROVAL
 FOR THE CURRENT CODE VERSION 2014. FL15210-R4 SUBMITTED
 IS FOR 2010 CODE VERSION.
  
 RESPONSE: PRODUCT APPROVAL WAS NOT SUBMITTED.
  
 3- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. COORDINATE WITH ITEM #1 ABOVE AND REVISE
 VALUATION AS REQUIRED.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]