| Date |
Text |
| 2015-09-16 16:13:04 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | 1. YOU SHALL PROVIDE A SITE PLAN INDICATING THE |
| | LOCATION OF THE MAIN SERVICE TO THE RESIDENCE. THOUGH |
| | ZONING HAS PERMITTED THE SECOND METER, NEC 230.2 ONLY |
| | PERMITS A SINGLE SERVICE PER STRUCTURE, AND FPL WILL |
| | GENERALLY ONLY HAVE A SINGLE DROP PER PROPERTY. |
| | 2. WHETHER YOU USE IT OR NOT, NEC 210.11(C) & 210.52(F) |
| | REQUIRE THAT YOU HAVE A DEDICATED LAUNDRY CIRCUIT. |
| | PROVIDE ONE ACCORDINGLY. |
| | 3. PER FBC-R 303.9, YOU SHALL PROVIDE HEAT CAPABLE OF |
| | MAINTAINING 68?F THREE FT. ABOVE THE FLOOR ETC. REVISE |
| | YOUR HVAC AND LOAD CALCS ACCORDINGLY. |
| | 4. NEC 406.12, REQUIRES THAT ALL 15 & 20 AMP |
| | NON-LOCKING RECEPTACLES IN DWELLING UNITS BE |
| | TAMPER-RESISTANT. |
| | 5. CORRECT YOUR LOAD CALCS TO MATCH PANEL SCHEDULE. |
| | FIGURE THE LOADS AS PER NEC 220.83. |
| | 6. NEC 314.27(A)(2), CEILING OUTLET BOXES SHALL BE |
| | LISTED TO SUPPORT A MINIMUM OF 50LBS. |
| | 7. NEC 314.27(C), REQUIRES THAT CEILING BOXES USED TO |
| | SUPPORT CEILING FANS BE LISTED AND MARKED FOR THE |
| | PURPOSE. |
| | 8. NEC 406.12, REQUIRES THAT 15 & 20 AMP RECEPTACLES IN |
| | WET LOCATIONS (OUTDOORS) BE LISTED WEATHER RESISTANT, |
| | ?WR?. |
| | 9. FBC-R SECTION 314, REQUIRES THAT YOU INSTALL SMOKE |
| | DETECTORS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |