2015-09-16 16:13:04PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. YOU SHALL PROVIDE A SITE PLAN INDICATING THE
 LOCATION OF THE MAIN SERVICE TO THE RESIDENCE. THOUGH
 ZONING HAS PERMITTED THE SECOND METER, NEC 230.2 ONLY
 PERMITS A SINGLE SERVICE PER STRUCTURE, AND FPL WILL
 GENERALLY ONLY HAVE A SINGLE DROP PER PROPERTY.
 2. WHETHER YOU USE IT OR NOT, NEC 210.11(C) & 210.52(F)
 REQUIRE THAT YOU HAVE A DEDICATED LAUNDRY CIRCUIT.
 PROVIDE ONE ACCORDINGLY.
 3. PER FBC-R 303.9, YOU SHALL PROVIDE HEAT CAPABLE OF
 MAINTAINING 68?F THREE FT. ABOVE THE FLOOR ETC. REVISE
 YOUR HVAC AND LOAD CALCS ACCORDINGLY.
 4. NEC 406.12, REQUIRES THAT ALL 15 & 20 AMP
 NON-LOCKING RECEPTACLES IN DWELLING UNITS BE
 TAMPER-RESISTANT.
 5. CORRECT YOUR LOAD CALCS TO MATCH PANEL SCHEDULE.
 FIGURE THE LOADS AS PER NEC 220.83.
 6. NEC 314.27(A)(2), CEILING OUTLET BOXES SHALL BE
 LISTED TO SUPPORT A MINIMUM OF 50LBS.
 7. NEC 314.27(C), REQUIRES THAT CEILING BOXES USED TO
 SUPPORT CEILING FANS BE LISTED AND MARKED FOR THE
 PURPOSE.
 8. NEC 406.12, REQUIRES THAT 15 & 20 AMP RECEPTACLES IN
 WET LOCATIONS (OUTDOORS) BE LISTED WEATHER RESISTANT,
 ?WR?.
 9. FBC-R SECTION 314, REQUIRES THAT YOU INSTALL SMOKE
 DETECTORS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  